AurFort
ETS 250LDanfoss ETS 250L — Electric expansion valve, manufacturer catalog image

Official Danfoss product image; the illustration may represent the product family.

ELECTRIC EXPANSION VALVE

ETS 250L — Electric expansion valve

SKU 034G3618

Danfoss ETS 250L (034G3618) — electric expansion valve for HVAC-R applications. Maximum working pressure: 37 bar. Compare the reference-specific connections, operating conditions and compatibility below. Send your quantity and delivery destination to AurFort for a quotation.

37 barMax. Working Pressure [bar]
1 5/8 inInlet size [in]
1 5/8 inOutlet size [in]
PRODUCT DATA

Technical specifications

Source: Danfoss product catalog.
Verified September 22, 2026.

034G3618 — selected manufacturer specifications
Gross weight2.012 Kilogram
Net weight1.901 Kilogram
Volume6.248 Liter
EAN5715162284940
TypeETS 250L
Product groupExpansion valves
Product Name DescriptionElectric expansion valve
Ambient temperature range [°C] [max]70 °C
Ambient temperature range [°C] [min]-40 °C
Ambient temperature range [°F] [max]158 °F
Ambient temperature range [°F] [min]-40 °F
ApprovalCE CMIM CRN EAC UA UKCA UL Recognized
Approval file nameMH7648
Balanced port [Yes/No]Yes
Body materialBrass
CE markYes
China RoHS complianceYes with exemptions
China RoHS exemption clause7.3
Compatible Danfoss controllersAK-XM 208C EKE EKF MCX
Connection Code(3002:X:41)
Connection materialCopper
Contains batteriesNo
Cv value [gal/min]16.1 gal/min
DirectionStraightway
Electrical conn. Male/FemaleMale
Electrical connectionM12
Electrical connection size4 pin
Enclosure rating IPIP67
EU RoHS complianceYes with exemptions
EU RoHS exemption clause6(c)
Flow characteristicLinear
Flow directionBi-flow
Flow direction indicatorArrow embossed
Fluid Group2
Full travel time CurrDrive [s]12.7 s
Full travel time VoltDrive [s]25.4 s
Inlet connection typeSolder ODF
Inlet size [in]1 5/8 in
Kv value [m³/h]13.9 m³/h
Lubricants compatibilityMO POE AB PAG PAO PVE
Manual operation optionAST-G service driver
Max allowed duty cycle [%]100 %
Max tot PowerCons CurrDrive[W]6.5 W
Max tot PowerCons VoltDrive[W]5.5 W
Max. Working Pressure [bar]37 bar
Max. Working Pressure [psig]536 psig
MaxOPD [bar]26 bar
MaxOPD [psi]377 psi
MaxOPD reverse CurrDrive [bar]17 bar
MaxOPD reverse CurrDrive [psi]247 psi
MaxOPD reverse VoltDrive [bar]12 bar
MaxOPD reverse VoltDrive [psi]174 psi
Motor typeBi-polar
MWP [bar] CRN32 bar
MWP [psig] CRN463 psig
Operating current max. [A]0.5 A
Outlet connection typeSolder ODF
Outlet size [in]1 5/8 in
Packing formatSingle pack
PED categoryI
Phase current (peak) [mA]283 mA
Phase current (RMS) [mA]200 mA
Phase inductance [µH]85000 μH
Product accessoriesStepper valve accessories
Quantity per packing format1 pc
Rated cap. cond. noteFull stroke open, normal flow
Rated cap. conditions [IMP]tcond=90 °F tevap=40 °F tliq=82 °F
Rated cap. conditions [SI]tcond=32 °C tevap=5 °C tliq=28 °C
Rated cap. R404A/R507A [kW]1037 kW
Rated cap. R404A/R507A [TR]295 TR
Rated capacity R134a [kW]724 kW
Rated capacity R134a [TR]206 TR
Rated capacity R407C [kW]1495 kW
Rated capacity R407C [TR]425 TR
Rated capacity R513A [kW]925 kW
Rated capacity R513A [TR]263 TR
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Refrigerant temperature [ºC] [max]70 °C
Refrigerant temperature [ºC] [min]-40 °C
Refrigerant temperature [ºF] [max]158 °F
Refrigerant temperature [ºF] [min]-40 °F
RefrigerantsR1234ze(E) R134a R22 R404A R407A R407C R407F R407H R410A R417A R422A R422B R422D R438A R442A R448A R449A R449B R450A R452A R463A R507A R513A R513B R515A R515B R1234yf
Resistance [kOhm]0.1 kOhm
SCIP dossier no.082963bf-1a44-410f-8480-cd924f065920
SCIP dossier product nameETS 175L-500L
ServiceableStepper valve spare parts
SightglassNo
Step mode2-phase full step
Total steps3810 (full steps)
UL approved refrigerantsR1234ze(E) R134a R22 R404A R407A R407C R407F R407H R410A R417A R422A R422B R422D R438A R442A R448A R449A R449B R450A R452A R463A R507A R513A R513B R515A R515B R1234yf
UL markYes
Voltage [V] DC12 V