Danfoss ETS 5M13L (034G6418) — electric expansion valve for HVAC-R applications. Maximum working pressure: 49 bar. Compare the reference-specific connections, operating conditions and compatibility below. Send your quantity and delivery destination to AurFort for a quotation.

49 barMax. Working Pressure [bar]
5/16 inInlet size [in]
5/16 inOutlet size [in]
PRODUCT DATA

Technical specifications

Source: Danfoss product catalog.
Verified September 22, 2026.

034G6418 — selected manufacturer specifications
Gross weight0.054 Kilogram
Net weight0.038 Kilogram
Volume0.251 Liter
EAN5715255005049
TypeETS 5M13L
Product groupExpansion valves
Product Name DescriptionElectric expansion valve
Ambient temperature range [°C] [max]70 °C
Ambient temperature range [°C] [min]-30 °C
Ambient temperature range [°F] [max]158 °F
Ambient temperature range [°F] [min]-22 °F
China RoHS complianceYes
China RoHS exemption clauseNo
Compatible Danfoss controllersEIM 336 EKE 1A EKE 1B EKE 1C EKE100
Connection Code(3002:X:6);(3001:X:6)
Connection materialCu-plated SS
Connection typeSolder, ODM
Contains batteriesNo
Design config. StyleL
EU RoHS complianceYes
EU RoHS exemption clauseNo
Flow characteristicLinear
Flow directionBi-flow
Inlet size [in]5/16 in
Inlet size [mm]7.94 mm
Lubricants compatibilityMO PAG POE PVE
Manual operation optionAST-G service driver Manual coil
Max. Leakage [cm³/min]150 cm³/min
Max. Working Pressure [bar]49 bar
Max. Working Pressure [psig]710 psig
MaxOPD [bar]42 bar
MaxOPD [psig]609 psig
MaxOPD reverse [bar]42 bar
MaxOPD reverse [psi]508 psi
Motor typePermanent magnet stepper motor
Orifice size [mm]1.3 mm
Outlet size [in]5/16 in
Outlet size [mm]7.94 mm
Packing formatMulti pack
Parts Program nameETS 5M
PED categoryArt. 4, par. 3
Product accessoriesElectric valve accessories
Quantity per packing format20 pc
Rated cap. conditions [SI]Subcooling=0 ºc Superheat=0 ºC tcond=38 ºC tevap=5 ºC
Rated cap. R404A/R507A [kW]5.29 kW
Rated cap. R404A/R507A [TR]1.5 TR
Rated capacity R1234yf [kW]4.2 kW
Rated capacity R1234yf [TR]1.19 TR
Rated capacity R1234ze(E) [kW]4.19 kW
Rated capacity R1234ze(E) [TR]1.19 TR
Rated capacity R134a [kW]5.76 kW
Rated capacity R134a [TR]1.64 TR
Rated capacity R22 [kW]7.5 kW
Rated capacity R22 [TR]2.13 TR
Rated capacity R290 [kW]7.83 kW
Rated capacity R290 [TR]2.23 TR
Rated capacity R32 [kW]13.07 kW
Rated capacity R32 [TR]3.72 TR
Rated capacity R407C [kW]7.91 kW
Rated capacity R407C [TR]2.25 TR
Rated capacity R407H [kW]8.83 kW
Rated capacity R407H [TR]2.51 TR
Rated capacity R410A [kW]8.85 kW
Rated capacity R410A [TR]2.52 TR
Rated capacity R448A [kW]7.55 kW
Rated capacity R448A [TR]2.15 TR
Rated capacity R449A [kW]7.38 kW
Rated capacity R449A [TR]2.1 TR
Rated capacity R449B [kW]7.5 kW
Rated capacity R449B [TR]2.13 TR
Rated capacity R452A [kW]5.67 kW
Rated capacity R452A [TR]1.61 TR
Rated capacity R452B [kW]10.18 kW
Rated capacity R452B [TR]2.89 TR
Rated capacity R454A [kW]7.64 kW
Rated capacity R454A [TR]2.17 TR
Rated capacity R454B [kW]10.3 kW
Rated capacity R454B [TR]2.93 TR
Rated capacity R454C [kW]6.6 kW
Rated capacity R454C [TR]1.88 TR
Rated capacity R455A [kW]7.27 kW
Rated capacity R455A [TR]2.07 TR
Rated capacity R513A [kW]4.86 kW
Rated capacity R513A [TR]1.38 TR
Rated capacity R515B [kW]4.06 kW
Rated capacity R515B [TR]1.15 TR
REACH Candidate List substancesNo
Refrigerant temperature [ºC] [max]80 °C
Refrigerant temperature [ºC] [min]-30 °C
Refrigerant temperature [ºF] [max]176 °F
Refrigerant temperature [ºF] [min]-22 °F
RefrigerantsR1234yf R1234ze(E) R134a R22 R290 R32 R404A/R507A R407C R407H R410A R448A R449A R449B R452A R452B R454A R454B R454C R455A R463A R513A R515B
Relative humidity (RH) [%] [max]95 %
Relative humidity (RH) [%] [min]0 %
ServiceableNo
Step mode1-2 excitation (half step) 2-2 excitation (full step)
Storage temperature range [°C] [max]70 °C
Storage temperature range [°C] [min]-30 °C
Storage temperature range [°F] [max]158 °F
Storage temperature range [°F] [min]-22 °F
Total steps480 (half steps)
Valve open pulses@normal flow55 ± 16 steps
Valve open pulses@reverse flow15 ± 15 steps
Valve versionV2