AurFort
ABBLS31P80L02-SABB LS31P80L02-S, manufacturer catalog image

ABB catalog image for this SKU; may represent the product family.

LIMIT SWITCH

LS31P80L02-S

SKU 1SBV030180R1302

ABB LS31P80L02-S: Limit Switch.

LS31P80L02-SProduct range
Limit SwitchProduct type
1SBV030180R1302Reference
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 09, 2026.

1SBV030180R1302 — selected manufacturer specifications
Product ID1SBV030180R1302
Catalog DescriptionLS31P80L02-S Limit Switch
Minimum Order Quantity10 piece
Customs Tariff Number85364900
Data Sheet, Technical Information1SBC141157C0202
Instructions and Manuals1SBC141157C0202
Product Net Width30 mm
Product Net Height90 mm
Product Net Depth / Length30 mm
Product Net Weight0.08 kg
Action Type of the Contact Element (acc. to IEC 60947-5-1)Simultaneous Slow Action Contacts
Actuation Speedacc. to IEC 60947-5-1 Max. 0.5 m/s acc. to IEC 60947-5-1 Min. 0.01 m/s
Angular Head Adjustmentadjustable head every 90°
B10d ValueOperations 30 Millions
Climatic Withstandaccording to IEC 68-2-3 and Salty Mist according to IEC 68-2-11
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-5-1, Θ = 40 °C 10 A
Connecting CapacityBar AWG 20 ... AWG 14 mm² Bar 0.5 ... 2.5 mm²
Consistency (Measured over 1 Million Operations)0.1 mm
Contact Element FormZb
Connecting Terminals (delivered in open position)M3.5 (+,-) pozidriv 2 screw with cable clamp
Degree of Protectionacc. to IEC 60529 IP65
Electrical Shock Protection acc. to IEC 536Double insulation - Class II
Flammability According to UL94V-0
Maximum Electrical Switching Frequency3600 cycles per hour (AC-15) 3600 cycles per hour (DC-13) 3600 cycles per hour
Mechanical Durability0 cycle
Mounting by Screws (not supplied)2 x M4 Screws
Movement to be Detectedsmall latch (key), front or vertical translation
Number of Auxiliary Contacts NC2
Number and Type of Bottom Cable GlandsPg 11 cable gland
Pilot Duty UL/CSAA600 Q600
Positive Opening Operation Force (Direct Opening Action)Minimum Force acc. to IEC 60947-5-1 30
Positive Opening Operation of NC Contact(s)Yes
Rated Impulse Withstand Voltage (Uimp)6 kV
Rated Operational Current AC-15 (Ie)(230 V AC) 3.1 A (400 V) NC 4 (24 V) 10 A (130 V) 5.5 A (240 V) 3 A
Rated Frequency (f)Supply Circuit 50 / 60 Hz
Rated Insulation Voltage (Ui)acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 400 V acc. to UL/CSA 600 V
Rated Operational Current DC-13 (Ie)(24 V) 6 A (110 V) 0.6 A (125 V) 0.55 A (250 V) 0.4 A
Resistance Between Contacts25 ms
Short-Circuit Protective DevicesgG Type Fuses 10 A
Terminal Markingaccording to EN 50013
Ambient Air TemperatureOperation -25 ... +70 °C Storage -30 ... +80 °C
Resistance to Shock acc. to IEC 60068-2-27Half-sine Pulse for 11 ms, No Change in Contact Position 10 m/s²
Resistance to VibrationsNo Change in Position of Contacts Greater than 100 µs: 5g 10 ... 500 Hz
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration1SBD251109E1001
RoHS DeclarationNo declaration needed
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA2CMT2023-006537
Environmental Product Declaration - EPDNo declaration needed
CQC CertificateCQC2004010305127663
cUL Certificate9AKK107991A7379
Declaration of Conformity - CCC2020980305001785
Declaration of Conformity - CE1SBD250883U1000
Declaration of Conformity - UKCA1SBD250886U1000
Package Level 1 Unitsbox 1 piece
Package Level 1 Width54 mm
Package Level 1 Depth / Length32 mm
Package Level 1 Height95 mm
Package Level 1 Gross Weight0.09 kg
Package Level 1 EAN3471522617040

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.