ABBT5N

ABB catalog image for this SKU; may represent the product family.
POWER CIRCUIT-BREAKER FOR TRAFO/GENERATOR/INSTALLATION PROTECTION
T5N 630 PR221DS-LS/I In=630 3p F F
SKU 1SDA054396R1ABB T5N 630 PR221DS-LS/I In=630 3p F F: Power circuit-breaker for trafo/generator/installation protection. Rated current: 630 A. Pole configuration: 3P.
630 ARated current
3PPoles
T5NProduct range
PRODUCT DATA
Technical specifications
Source: ABB English regional product catalog.
Verified September 15, 2026.
| Product ID | 1SDA054396R1 |
|---|---|
| Catalog Description | T5N 630 PR221DS-LS/I In=630 3p F F |
| Country of Origin | India |
| Made To Order | No |
| Warranty Return | Product under warranty must be returned |
| Product Sales Status | Active |
| Quote Only | No |
| Stocked At Warehouses | INABB015EXPU |
| Environmental Product Declaration - EPD | No declaration needed |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| Environmental Information | 9AKK10103A1056 9AKK108467A6707 |
| E-Number (Finland) | 3655323 |
| E-Number (Norway) | 4383613 |
| E-Number (Sweden) | 3180374 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Product Net Width | 140 mm |
| Product Net Height | 205 mm |
| Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 4.817 kg |
| Package Level 1 Units | 1 piece |
| Package Level 1 Width | 248 mm |
| Package Level 1 Height | 240 mm |
| Package Level 1 Depth / Length | 285 mm |
| Package Level 1 Gross Weight | 5.1 kg |
| Package Level 1 EAN | 8015644554941 |
| Product Main Type | SACE Tmax T |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Suitable For | T5 |
| Suitable for Product Class | Moulded Case Circuit Breakers |
| Version | F |
| Electrical Durability | 5000 cycle 60 cycles per hour |
| Mechanical Durability | 20000 cycle 120 cycles per hour |
| Number of Poles | 3P |
| Power Loss | at Rated Operating Conditions per Pole 41 W |
| Rated Current (In) | 630 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 70 kA (230 V AC) 70 kA (380 V AC) 36 kA (400 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 30 kA (500 V AC) 25 kA (690 V AC) 20 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 70 kA (230 V AC) 70 kA (380 V AC) 36 kA (400 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 30 kA (500 V AC) 25 kA (690 V AC) 20 kA |
| Rated Uninterrupted Current (Iu) | 630 A |
| Release | PR221DS-LS/I |
| Release Type | EL |
| Short-Circuit Performance Level | N |
| Standards | IEC |
| Sub-type | T5 |
| Terminal Connection Type | Fixed Circuit-Breakers Front |
| Test Voltage Max (Utest) | 3500 V |
| Test Voltage at Industrial Frequency for 1 Minute | 3500 V |
| Data Sheet, Technical Information | 1SDC210004D0203 |
| Declaration of Conformity - CE | 9AKK106713A5539 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| Instructions and Manuals | 1SDH000437R0001 |
| Instructions and Manuals (Part 2) | ITSCE-RH0100001 |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.