AurFort
ABBT7SABB T7S 1250 PR231/P LS/I In=1250A 4p F F, manufacturer catalog image

ABB catalog image for this SKU; may represent the product family.

POWER CIRCUIT-BREAKER FOR TRAFO/GENERATOR/INSTALLATION PROTECTION

T7S 1250 PR231/P LS/I In=1250A 4p F F

SKU 1SDA062874R1

ABB T7S 1250 PR231/P LS/I In=1250A 4p F F: Power circuit-breaker for trafo/generator/installation protection. Rated current: 1250 A. Pole configuration: 4P.

1250 ARated current
4PPoles
T7SProduct range
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 15, 2026.

1SDA062874R1 — selected manufacturer specifications
Product ID1SDA062874R1
Catalog DescriptionT7S 1250 PR231/P LS/I In=1250A 4p F F
Country of OriginIndia
Made To OrderNo
Warranty ReturnProduct under warranty must be returned
Product Sales StatusActive
Quote OnlyNo
Stocked At WarehousesINABB015EXPU
Environmental Product Declaration - EPDNo declaration needed
REACH Declaration9AKK108466A1425
RoHS Declaration9AKK108466A1424
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
Toxic Substances Control Act - TSCA9AKK108467A8326
Environmental Information9AKK10103A1059 9AKK108467A6707
Minimum Order Quantity1 piece
Customs Tariff Number85362090
Product Net Width280 mm
Product Net Height268 mm
Product Net Depth / Length154 mm
Product Net Weight17.67 kg
Package Level 1 Units1 piece
Package Level 1 Width360 mm
Package Level 1 Height350 mm
Package Level 1 Depth / Length360 mm
Package Level 1 Gross Weight18.6 kg
Package Level 1 EAN8015644654238
Product Main TypeSACE Tmax T
Product NameMoulded Case Circuit Breaker
Product TypeAutomatic Circuit Breaker
Suitable ForT7
Suitable for Product ClassMoulded Case Circuit Breakers
VersionF
Electrical Durability2000 cycle 60 cycles per hour
Mechanical Durability10000 cycle 60 cycles per hour
Number of Poles4P
Power Lossat Rated Operating Conditions per Pole 47 W
Rated Current (In)1250 A
Rated Impulse Withstand Voltage (Uimp)8 kV
Rated Insulation Voltage (Ui)1000 V
Rated Operational Voltage690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 85 kA (230 V AC) 85 kA (380 V AC) 50 kA (400 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 40 kA (690 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(220 V AC) 85 kA (230 V AC) 85 kA (380 V AC) 50 kA (400 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 40 kA (690 V AC) 30 kA
Rated Uninterrupted Current (Iu)1250 A
ReleasePR231/P-LS/I
Release TypeEL
Short-Circuit Performance LevelS
StandardsIEC
Sub-typeT7
Terminal Connection TypeFixed Circuit-Breakers Front
Data Sheet, Technical Information1SDC210015D0201
Declaration of Conformity - CE9AKK106713A5537
EU Data Act Compliance Declaration1SDH002560A1001
GL Certificate1SDL000163R0055
Instructions and Manuals1SDC210015D0201

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.