POWER CIRCUIT-BREAKER FOR TRAFO/GENERATOR/INSTALLATION PROTECTION

T7S 1600 PR231/P LS/I In=1600A 3p F F

SKU 1SDA062994R1

ABB T7S 1600 PR231/P LS/I In=1600A 3p F F: Power circuit-breaker for trafo/generator/installation protection. Rated current: 1600 A. Pole configuration: 3P.

1600 ARated current
3PPoles
T7SProduct range
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 15, 2026.

1SDA062994R1 — selected manufacturer specifications
Product ID1SDA062994R1
Catalog DescriptionT7S 1600 PR231/P LS/I In=1600A 3p F F
Country of OriginIndia
Made To OrderNo
Warranty ReturnProduct under warranty must be returned
Product Sales StatusActive
Quote OnlyNo
Stocked At WarehousesINABB015EXPU
Environmental Product Declaration - EPDNo declaration needed
REACH Declaration9AKK108466A1425
RoHS Declaration9AKK108466A1424
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
Toxic Substances Control Act - TSCA9AKK108467A8326
Environmental Information9AKK10103A1059 9AKK108467A6707
Minimum Order Quantity1 piece
Customs Tariff Number85362090
Product Net Width210 mm
Product Net Height268 mm
Product Net Depth / Length154 mm
Product Net Weight13.614 kg
Package Level 1 Units1 piece
Package Level 1 Width280 mm
Package Level 1 Height350 mm
Package Level 1 Depth / Length360 mm
Package Level 1 Gross Weight14.33 kg
Package Level 1 EAN8015644655433
Product Main TypeSACE Tmax T
Product NameMoulded Case Circuit Breaker
Product TypeAutomatic Circuit Breaker
Suitable ForT7
Suitable for Product ClassMoulded Case Circuit Breakers
VersionF
Electrical Durability2000 cycle 60 cycles per hour
Gross Volume35,280 cm³
Mechanical Durability10000 cycle 60 cycles per hour
Number of Poles3P
Power Lossat Rated Operating Conditions per Pole 77 W
Rated Current (In)1600 A
Rated Impulse Withstand Voltage (Uimp)8 kV
Rated Insulation Voltage (Ui)1000 V
Rated Operational Voltage690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 85 kA (230 V AC) 85 kA (380 V AC) 50 kA (400 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 40 kA (690 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(220 V AC) 85 kA (230 V AC) 85 kA (380 V AC) 50 kA (400 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 40 kA (690 V AC) 30 kA
Rated Uninterrupted Current (Iu)1600 A
ReleasePR231/P-LS/I
Release TypeEL
Short-Circuit Performance LevelS
StandardsIEC
Sub-typeT7
Terminal Connection TypeFixed Circuit-Breakers Front
Data Sheet, Technical Information1SDC210015D0201
Declaration of Conformity - CE9AKK106713A5537
EU Data Act Compliance Declaration1SDH002560A1001
GL Certificate1SDL000163R0055
Instructions and Manuals1SDC210015D0201

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.