AurFort
ABBA3SABB A3S 400 TMF 400-4000 3p F F, manufacturer catalog image

ABB catalog image for this SKU; may represent the product family.

POWER CIRCUIT-BREAKER FOR TRAFO/GENERATOR/INSTALLATION PROTECTION

A3S 400 TMF 400-4000 3p F F

SKU 1SDA066563R1

ABB A3S 400 TMF 400-4000 3p F F: Power circuit-breaker for trafo/generator/installation protection. Rated current: Main Circuit 400 A. Pole configuration: 3P.

Main Circuit 400 ARated current
3PPoles
A3SProduct range
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 08, 2026.

1SDA066563R1 — selected manufacturer specifications
Product ID1SDA066563R1
Catalog DescriptionA3S 400 TMF 400-4000 3p F F
Country of OriginIndia
Made To OrderNo
Warranty ReturnProduct under warranty must be returned
Product Sales StatusActive
Quote OnlyNo
Stocked At WarehousesINABB015EXPU
REACH Declaration9AKK108466A1425
RoHS Declaration9AKK108466A1424
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
Toxic Substances Control Act - TSCA9AKK108467A8326
SCIPb29110dc-a466-474d-aa87-27b29ff2d11b Italy
Simplified SCIP81e1434b-3835-4f99-bd1a-197a8265cb23 Germany 25d2b083-9d62-4b8d-90e9-8f3de05ca532 Poland 9876a560-b8fa-47be-9e9d-7cbfae45f4a9 Sweden 1a44c327-b703-4181-815a-9d35406e2a4f Germany 507defc2-6189-412a-83ba-33d4df333d77 Germany 2b7258ce-e8d1-4d88-bb8f-075b254b2a85 Croatia b67be9e3-de80-4f83-a405-41e512516561 Czechia 1f25ceae-f96a-4900-b0c9-296bcde2e889 Poland e6b4027d-4df5-40ed-8055-356636edacd7 Netherlands 1517c6f9-f8ea-4dc7-ae42-90a6acd214cd Netherlands a0ea08be-642e-4607-b2e9-a61c6f370da9 Germany 6219f5da-c800-44cb-a362-5294a9cbe968 Denmark d4da7e87-755b-4de0-85af-f1611112c34c Germany 6e633f2a-4c17-4848-befb-45721fde65d4 Poland 8181a142-a57b-4bf0-ba19-eb9bc5c1169c Norway d9654006-3a8c-4546-a173-e6453224de04 Finland 290cf4b8-5af6-492f-a1a6-501a0634c914 France 164976e3-2e34-4b90-8ae9-e98707c75a10 Netherlands 838acc23-8bdb-4ad4-8ec8-e68c18759e47 Spain 076c9fdf-3e25-4863-b9c4-0667b1a6164d Netherlands c7561e5e-ddbd-4df2-87a9-3f4ffb6a1fce Portugal ff065024-89e3-457d-acd0-06c4d49be3c8 France 40ea8737-d80d-4ecb-8a23-bc67e8dc4ecc Bulgaria c4e1422f-88fa-48c6-a63e-7338c844e018 Sweden 74bc2474-107f-4db2-a97e-2936086e5134 Netherlands f844a7c4-3868-45e1-b8a4-0888f3343150 Estonia c1b558bc-2516-4a87-8e3c-e91342c37807 Greece
Environmental Information1SDL000185R001 9AKK108467A6707
Order Code US and CanadaACS400TW
Minimum Order Quantity1 piece
Customs Tariff Number85362090
Product Net Width139.5 mm
Product Net Height205 mm
Product Net Depth / Length103.5 mm
Product Net Weight4.575 kg
Package Level 1 Units1 piece
Package Level 1 Width286 mm
Package Level 1 Height228 mm
Package Level 1 Depth / Length244 mm
Package Level 1 Gross Weight4.85 kg
Package Level 1 EAN8015644004750
Product Main TypeSACE FORMULA
Product NameMoulded Case Circuit Breaker
Product TypeAutomatic Circuit Breaker
VersionF
Electrical Durability2000 cycle
Mechanical Durability5000 cycle
Number of Poles3P
Opening TimeCB with SOR 15 ms CB with UVR ≤25 ms
Power Lossat Rated Operating Conditions per Pole 19.5 W
Rated Current (In)Main Circuit 400 A
Rated Impulse Withstand Voltage (Uimp)6 kV
Rated Insulation Voltage (Ui)690 V
Rated Operational Voltage550 V AC 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)(240 V AC) 50 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 25 kA (480 V AC) 17.5 kA (500 V AC) 12.5 kA (250 V DC) 2 Poles in Series 25 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(240 V AC) 100 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (480 V AC) 35 kA (500 V AC) 25 kA (250 V DC) 2 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)400 A
ReleaseTMF
Release TypeTM
Short-Circuit Performance LevelS
StandardsIEC
Sub-typeA3
Terminal Connection TypeFront
Data Sheet, Technical Information1SDC210032D0204
Declaration of Conformity - CE9AKK106713A5517
Wiring Diagram1SDM000079R0001
Instructions and Manuals1SDH000747R0001

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.