ABB A3N 630 TMF 500-5000 3p F F: Power circuit-breaker for trafo/generator/installation protection. Rated current: Main Circuit 500 A. Pole configuration: 3P.

Main Circuit 500 ARated current
3PPoles
A3NProduct range
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 08, 2026.

1SDA066564R1 — selected manufacturer specifications
Product ID1SDA066564R1
Catalog DescriptionA3N 630 TMF 500-5000 3p F F
Country of OriginIndia
Made To OrderNo
Warranty ReturnProduct under warranty must be returned
Product Sales StatusActive
Quote OnlyNo
Stocked At WarehousesINABB015EXPU
REACH Declaration9AKK108466A1425
RoHS Declaration9AKK108466A1424
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
Toxic Substances Control Act - TSCA9AKK108467A8326
SCIP5c296776-176a-4b99-b75b-317e2f13dc2e Italy
Simplified SCIPfa2a5242-ee83-4762-b25f-85e324f60ea7 Poland d712e1f0-eb0d-4463-ac43-fde39596be1b Estonia de57fc0a-bb64-4bb5-8703-18afd0d04953 Greece 3b5572c6-d6d3-4ebe-874c-491d115c98cf Croatia 93b77151-52cc-4a21-93ca-f298b95b9b03 Germany cdc19278-eede-4ee0-ab8e-d56f9e24bcea Germany 9d642647-c9eb-4dad-99f6-b21d985e3c76 Denmark b3aabbc7-d774-464f-98f5-28a6a86c01c7 Sweden 207ecdef-6349-4ace-b9f8-4edd00d9f7fb France 12facbff-c733-428c-84af-a482eda8b2ba Germany 990f1fe1-abc1-4c7c-9f6b-481f03944514 Hungary 3f303ddc-bb9b-4fd2-a5a8-1569f101a588 Spain 5f6388ae-097f-4393-8558-15652409e5ee Belgium 88779175-50e9-49dc-9897-0ad18f7f2800 Germany 008506ec-6aba-477e-9540-e4db5bbc959b France f66859c8-a550-4e61-bea1-1b1195686311 Czechia 301948a5-9402-4e19-9222-575aea7555ee Portugal 9e9a3350-1db9-4043-b570-ff35c10c6a83 Germany 5c426144-d88a-40e2-9af0-2b4398ac26c3 Poland 82021251-0c55-4795-a60a-487c47761a24 Poland 529c1aed-a978-4ba4-99bf-75946600e10d Bulgaria babe1911-6cc3-4ad9-b34f-ae1713bb430a Norway d460aa5c-cecf-413a-9440-d1e04f9309e4 Netherlands caad674f-c6cd-4f3e-adce-1cf2d564a555 Sweden 7e38eb3a-a547-4315-b4b4-b87b223682db Finland 54744cc1-d04d-4c66-9593-257c9d7eb9e5 Hungary f02d2c84-7d78-4c38-a6ef-e82a79160fc7 Belgium
Environmental Information1SDL000185R001 9AKK108467A6707
Minimum Order Quantity1 piece
Customs Tariff Number85362090
Product Net Width139.5 mm
Product Net Height205 mm
Product Net Depth / Length103.5 mm
Product Net Weight4.589 kg
Package Level 1 Units1 piece
Package Level 1 Width286 mm
Package Level 1 Height228 mm
Package Level 1 Depth / Length244 mm
Package Level 1 Gross Weight4.85 kg
Package Level 1 EAN8015644004767
Product Main TypeSACE FORMULA
Product NameMoulded Case Circuit Breaker
Product TypeAutomatic Circuit Breaker
VersionF
Electrical Durability2000 cycle
Mechanical Durability5000 cycle
Number of Poles3P
Opening TimeCB with SOR 15 ms CB with UVR ≤25 ms
Power Lossat Rated Operating Conditions per Pole 28.8 W
Rated Current (In)Main Circuit 500 A
Rated Impulse Withstand Voltage (Uimp)6 kV
Rated Insulation Voltage (Ui)690 V
Rated Operational Voltage550 V AC 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)(240 V AC) 42.5 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 18 kA (480 V AC) 12.5 kA (500 V AC) 10 kA (250 V DC) 2 Poles in Series 18 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(240 V AC) 85 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (480 V AC) 25 kA (500 V AC) 20 kA (250 V DC) 2 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)630 A
ReleaseTMF
Release TypeTM
Short-Circuit Performance LevelN
StandardsIEC
Sub-typeA3
Terminal Connection TypeFront
Data Sheet, Technical Information1SDC210032D0204
Declaration of Conformity - CE9AKK106713A5517
Wiring Diagram1SDM000079R0001
Instructions and Manuals1SDH000747R0001