AurFort
ABBA3SABB A3S 630 ELT-LI In=630 3p F F, manufacturer catalog image

ABB catalog image for this SKU; may represent the product family.

POWER CIRCUIT-BREAKER FOR TRAFO/GENERATOR/INSTALLATION PROTECTION

A3S 630 ELT-LI In=630 3p F F

SKU 1SDA066567R1

ABB A3S 630 ELT-LI In=630 3p F F: Power circuit-breaker for trafo/generator/installation protection. Rated current: Main Circuit 630 A. Pole configuration: 3P.

Main Circuit 630 ARated current
3PPoles
A3SProduct range
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 08, 2026.

1SDA066567R1 — selected manufacturer specifications
Product ID1SDA066567R1
Catalog DescriptionA3S 630 ELT-LI In=630 3p F F
Country of OriginIndia
Made To OrderNo
Warranty ReturnProduct under warranty must be returned
Product Sales StatusActive
Quote OnlyNo
Stocked At WarehousesINABB015EXPU
REACH Declaration9AKK108466A1425
RoHS Declaration9AKK108466A1424
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
Toxic Substances Control Act - TSCA9AKK108467A8326
SCIPa5e5d95f-5f41-421f-a680-e259ffbf0a61 Italy
Simplified SCIPe9ae25ab-dd9e-4739-899b-586faffde463 Denmark ee082392-e73a-4c82-b7e5-c6876fb87351 Sweden c0289686-ee98-45e9-89ca-d7b56c56afa4 Germany 83269372-0832-4172-aaf8-75b67a72d070 Estonia b81217ca-3a00-4ede-8703-20dafb7a9aaa Netherlands 2a2e646c-6412-47f0-827d-12223b669393 Bulgaria ac58a438-117c-4689-b136-0e3b0c8b00ee Norway 8ee415e5-9f7a-4272-bcdb-b2c85082ed77 Sweden 0af5241f-167a-46b9-9e2c-a51f260ef752 Poland 19657a69-8a3c-4143-b52d-0986a91b361f France 9d6e8000-1483-4964-8b47-de406a63a437 Belgium 04f79e23-e120-4065-919e-e8abb1c1c519 Poland 5331926b-83f3-4d33-b290-9ec8e6077549 Hungary f305d25f-4129-4335-9215-2aaf81a580ed Belgium f8937102-e08f-4310-8130-19a386e2ad28 Germany 87674700-c17d-4743-ba58-100ee70cf1c7 Croatia 90882139-8f92-46a6-83dd-adde492ecf82 Finland 0509b07a-d39a-4442-aeb3-1672b4c9ff47 Czechia 7e3083f5-454b-4061-b61f-7e118ecd64e5 Greece 7ffe409a-314a-4599-960c-87124ae8db12 Poland 75c86522-001a-4ea6-8301-52d3a154f9b8 Germany 95618630-8392-4b81-a526-b320a60c9aaf Germany 279fc966-badf-46b9-8ed5-7e6dda2c06b7 Portugal 3ec14fad-c443-4014-b0c7-283b5f519e6e Spain 6c5faf00-9a43-4b3c-9255-f685c5aa38a0 Germany 4a48e741-5bc1-4aa4-a0ec-e59c610e7cdb Hungary 0910c2e4-1c41-44ef-b8f6-d7327577c9fc France
Environmental Information1SDL000184R0001 9AKK108467A6707
Order Code US and CanadaADS630AW
Minimum Order Quantity1 piece
Customs Tariff Number85362090
Product Net Width139.5 mm
Product Net Height205 mm
Product Net Depth / Length103.5 mm
Product Net Weight4.84 kg
Package Level 1 Units1 piece
Package Level 1 Width286 mm
Package Level 1 Height228 mm
Package Level 1 Depth / Length244 mm
Package Level 1 Gross Weight4.85 kg
Package Level 1 EAN8015644693329
Product Main TypeSACE FORMULA
Product NameMoulded Case Circuit Breaker
Product TypeAutomatic Circuit Breaker
VersionF
Electrical Durability2000 cycle
Mechanical Durability5000 cycle
Number of Poles3P
Opening TimeCB with SOR 15 ms CB with UVR ≤25 ms
Power Lossat Rated Operating Conditions per Pole 41 W
Rated Current (In)Main Circuit 630 A
Rated Impulse Withstand Voltage (Uimp)6 kV
Rated Insulation Voltage (Ui)690 V
Rated Operational Voltage550 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)(240 V AC) 50 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 25 kA (480 V AC) 17.5 kA (500 V AC) 12.5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(240 V AC) 100 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (480 V AC) 35 kA (500 V AC) 25 kA (250 V DC) 2 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)630 A
ReleaseELT LI
Release TypeEL
Short-Circuit Performance LevelS
StandardsIEC
Sub-typeA3
Terminal Connection TypeFront
Data Sheet, Technical Information1SDC210032D0204
Declaration of Conformity - CE9AKK106713A5517
Wiring Diagram1SDM000079R0001
Instructions and Manuals1SDH000747R0001

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.