AurFort
ABBA3NABB A3N 400 TMF 320-3200 4p F F InN=100%In, manufacturer catalog image

ABB catalog image for this SKU; may represent the product family.

POWER CIRCUIT-BREAKER FOR TRAFO/GENERATOR/INSTALLATION PROTECTION

A3N 400 TMF 320-3200 4p F F InN=100%In

SKU 1SDA066568R1

ABB A3N 400 TMF 320-3200 4p F F InN=100%In: Power circuit-breaker for trafo/generator/installation protection. Rated current: Main Circuit 320 A. Pole configuration: 4P.

Main Circuit 320 ARated current
4PPoles
A3NProduct range
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 08, 2026.

1SDA066568R1 — selected manufacturer specifications
Product ID1SDA066568R1
Catalog DescriptionA3N 400 TMF 320-3200 4p F F InN=100%In
Country of OriginIndia
Made To OrderNo
Warranty ReturnProduct under warranty must be returned
Product Sales StatusActive
Quote OnlyNo
Stocked At WarehousesINABB015EXPU
REACH Declaration9AKK108466A1425
RoHS Declaration9AKK108466A1424
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
Toxic Substances Control Act - TSCA9AKK108467A8326
SCIP303549c0-095d-4ad6-85b3-f240eb58fe9e Italy
Simplified SCIPaab0dd13-8942-4264-b12b-0602d45f4300 Belgium 3fc02d4f-f173-4677-81d6-c4f97bf72ac1 Spain cceb0483-1f24-434f-893e-c6a0d90d9ac6 Hungary cdd30fc5-eeec-4bf3-96eb-dcce8831b694 France e4030675-f373-4ffd-8264-45e9d4252c89 Germany c3cec60e-ede0-4cf2-b71a-dba8a36464bc Croatia 98a2c8c8-e925-48ad-a71a-ed56fabb6c61 Germany c19fb3e6-4193-41bc-aff7-3ba96afefa09 Sweden f1fd59da-2267-4578-81dc-1c23f60d10ce Germany cdfa37f2-2e8b-45b8-ba83-7f4daf678075 Denmark ecf341f9-0b09-4d3e-99dd-85582d57107d Poland 62ef4264-9b5b-4dd3-9964-8a44f1a34c57 Portugal 4df6111a-54a1-45bd-94dd-a7ea21a25c0b Bulgaria b79bded3-3205-4405-a3c9-f9be7986642f Poland cb7634ca-df18-44e4-b138-5d2458f6ef84 Sweden a5660347-4639-41c3-839c-0c3314ff3fa1 Norway ca30b75f-8915-47f6-abe6-6a8c739782ac Netherlands 6c6ed68e-df6a-4782-ac49-1c457cb622a1 Czechia 5d412063-dde1-43d7-8c6a-50ef343a5ebf Germany f2ece032-1598-45a5-b2c1-3e0dd5e7b126 Finland 60d2b28f-0621-4186-b89f-0874608a1cf7 Estonia 0192910d-3b54-4d31-a46d-72df7be89bf6 Poland d36f7619-14d2-45f0-8709-bac05c828ea1 Hungary 697d2423-3b49-45d8-a9e0-d24bffb10507 Belgium 82cbcbd3-2b4e-452e-8a45-5f56d587efd8 France eed33b9f-ae1b-4b92-96ca-71f7bdcb46c2 Greece 2dd3d2c4-1a83-4985-acaa-24f380780075 Germany
Environmental Information1SDL000185R001 9AKK108467A6707
Minimum Order Quantity1 piece
Customs Tariff Number85362090
Product Net Width186 mm
Product Net Height205 mm
Product Net Depth / Length103.5 mm
Product Net Weight6.4 kg
Package Level 1 Units1 piece
Package Level 1 Width286 mm
Package Level 1 Height228 mm
Package Level 1 Depth / Length244 mm
Package Level 1 Gross Weight6.5 kg
Package Level 1 EAN8015644004804
Product Main TypeSACE FORMULA
Product NameMoulded Case Circuit Breaker
Product TypeAutomatic Circuit Breaker
VersionF
Electrical Durability2000 cycle
Mechanical Durability5000 cycle
Number of Poles4P
Opening TimeCB with SOR 15 ms CB with UVR ≤25 ms
Power Lossat Rated Operating Conditions per Pole 13.6 W
Rated Current (In)Main Circuit 320 A
Rated Impulse Withstand Voltage (Uimp)6 kV
Rated Insulation Voltage (Ui)690 V
Rated Operational Voltage550 V AC 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)(240 V AC) 42.5 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 18 kA (480 V AC) 12.5 kA (500 V AC) 10 kA (250 V DC) 2 Poles in Series 18 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(240 V AC) 85 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (480 V AC) 25 kA (500 V AC) 20 kA (250 V DC) 2 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)400 A
ReleaseTMF
Release TypeTM
Short-Circuit Performance LevelN
StandardsIEC
Sub-typeA3
Terminal Connection TypeFront
Data Sheet, Technical Information1SDC210032D0204
Declaration of Conformity - CE9AKK106713A5517
Wiring Diagram1SDM000079R0001
Instructions and Manuals1SDH000747R0001

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.