ABBA3N

ABB catalog image for this SKU; may represent the product family.
POWER CIRCUIT-BREAKER FOR TRAFO/GENERATOR/INSTALLATION PROTECTION
A3N 630 TMF 500-5000 4p F F InN=100%In
SKU 1SDA066572R1ABB A3N 630 TMF 500-5000 4p F F InN=100%In: Power circuit-breaker for trafo/generator/installation protection. Rated current: Main Circuit 500 A. Pole configuration: 4P.
Main Circuit 500 ARated current
4PPoles
A3NProduct range
PRODUCT DATA
Technical specifications
Source: ABB English regional product catalog.
Verified September 08, 2026.
| Product ID | 1SDA066572R1 |
|---|---|
| Catalog Description | A3N 630 TMF 500-5000 4p F F InN=100%In |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 4e7d3ec8-3cd7-431e-95dd-dd8056a9292a Italy |
| Simplified SCIP | fdba9d77-d8ae-4078-8ab8-d0e30ee93361 Germany 7d9c021c-2d41-4e26-9f3b-cf6602e55a94 Croatia f299de1e-d0be-400c-9b4e-4a71e14ae10d Germany b81b82ac-2f16-486a-a4f2-64bc47211817 Sweden 4e182031-9823-47d2-82f3-e66a7a2012d2 Germany 7b07eb41-82fe-422f-9e02-0533bd8ac0eb Denmark db8c5f18-a6e8-457a-ba65-baeb2323290c Belgium 6fc860dd-75eb-4e61-b4f7-199f69bdeec1 Greece cec93e25-6264-46f3-8fec-50bc33f2fc78 Germany f2df26da-a287-4412-98cd-f995cce7ccf0 France c97af4cc-2233-49a9-bf80-8222313d3d31 Spain 8d7965a4-b227-4c1f-a860-1e7b2a3e2778 Hungary 6c277aec-3adb-48d5-aff7-015bb35b37f4 Belgium 280da499-5a85-45a2-820f-2570613de86b France 3d231017-0a7c-47ef-a3ab-267ac775e16e Germany 1d14cd28-8715-48ba-b001-f6b2841cb7b6 Czechia 90c5ee85-d7dc-4ce0-9e75-5fd57abe6a6b Poland 30f42318-d1bd-49f7-ba1e-c04ca26457a5 Poland 9ed6144b-44d2-412a-9c1b-56c61e4836e5 Bulgaria 4d74ad76-52f2-46fb-96cd-46caddecf6f1 Netherlands 6c758992-103a-44ac-b37b-00b8844f3ca5 Portugal d7c39903-fdaf-4682-9af0-6a8cdcbd681d Sweden 5671bd3b-6696-4b42-9895-63925a7ea806 Norway 09026be0-a242-4af2-8d39-5865db87e5a6 Hungary 6cc66eb8-e105-4d85-bbd4-0b7ad0d052cf Finland 1d996aea-55a2-4bce-8e49-a54c329e9bd1 Poland 259e1c17-fef5-4f32-8172-100c15a4fa40 Estonia |
| Environmental Information | 1SDL000185R001 9AKK108467A6707 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Product Net Width | 186 mm |
| Product Net Height | 205 mm |
| Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 6.4 kg |
| Package Level 1 Units | 1 piece |
| Package Level 1 Width | 286 mm |
| Package Level 1 Height | 228 mm |
| Package Level 1 Depth / Length | 244 mm |
| Package Level 1 Gross Weight | 6.5 kg |
| Package Level 1 EAN | 8015644004842 |
| Product Main Type | SACE FORMULA |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Version | F |
| Electrical Durability | 2000 cycle |
| Mechanical Durability | 5000 cycle |
| Number of Poles | 4P |
| Opening Time | CB with SOR 15 ms CB with UVR ≤25 ms |
| Power Loss | at Rated Operating Conditions per Pole 28.8 W |
| Rated Current (In) | Main Circuit 500 A |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Rated Insulation Voltage (Ui) | 690 V |
| Rated Operational Voltage | 550 V AC 250 V DC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (240 V AC) 42.5 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 18 kA (480 V AC) 12.5 kA (500 V AC) 10 kA (250 V DC) 2 Poles in Series 18 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (240 V AC) 85 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (480 V AC) 25 kA (500 V AC) 20 kA (250 V DC) 2 Poles in Series 36 kA |
| Rated Uninterrupted Current (Iu) | 630 A |
| Release | TMF |
| Release Type | TM |
| Short-Circuit Performance Level | N |
| Standards | IEC |
| Sub-type | A3 |
| Terminal Connection Type | Front |
| Data Sheet, Technical Information | 1SDC210032D0204 |
| Declaration of Conformity - CE | 9AKK106713A5517 |
| Wiring Diagram | 1SDM000079R0001 |
| Instructions and Manuals | 1SDH000747R0001 |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.