POWER CIRCUIT-BREAKER FOR TRAFO/GENERATOR/INSTALLATION PROTECTION

A2N 250 TMF 250-2500 4p F F

SKU 1SDA066798R1

ABB A2N 250 TMF 250-2500 4p F F: Power circuit-breaker for trafo/generator/installation protection. Rated current: Main Circuit 250 A. Pole configuration: 4P.

Main Circuit 250 ARated current
4PPoles
A2NProduct range
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 08, 2026.

1SDA066798R1 — selected manufacturer specifications
Product ID1SDA066798R1
Catalog DescriptionA2N 250 TMF 250-2500 4p F F
Country of OriginIndia
Made To OrderNo
Warranty ReturnProduct under warranty must be returned
Product Sales StatusActive
Quote OnlyNo
Stocked At WarehousesINABB015EXPU
REACH Declaration9AKK108466A1425
RoHS Declaration9AKK108466A1424
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
Toxic Substances Control Act - TSCA9AKK108467A8326
Environmental Information1SDL000183R0001 9AKK108467A6707
Order Code US and CanadaABN250TW-4
Minimum Order Quantity1 piece
Customs Tariff Number85362090
Product Net Width140 mm
Product Net Height150 mm
Product Net Depth / Length60 mm
Product Net Weight1.75 kg
Package Level 1 Units1 piece
Package Level 1 Width162 mm
Package Level 1 Height120 mm
Package Level 1 Depth / Length155 mm
Package Level 1 Gross Weight1.8 kg
Package Level 1 EAN8015644694449
Product Main TypeSACE FORMULA
Product NameMoulded Case Circuit Breaker
Product TypeAutomatic Circuit Breaker
VersionF
Electrical Durability4000 cycle
Mechanical Durability10000 cycle
Number of Poles4P
Opening TimeCB with SOR 15 ms CB with UVR 15 ms
Power Lossat Rated Operating Conditions per Pole 16 W
Rated Current (In)Main Circuit 250 A
Rated Impulse Withstand Voltage (Uimp)6 kV
Rated Insulation Voltage (Ui)690 V
Rated Operational Voltage550 V AC 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)(240 V AC) 42.5 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 12.5 kA (480 V AC) 12.5 kA (500 V AC) 5 kA (250 V DC) 2 Poles in Series 18 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(240 V AC) 85 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 25 kA (480 V AC) 25 kA (500 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)250 A
ReleaseTMF
Release TypeTM
Short-Circuit Performance LevelN
StandardsIEC
Sub-typeA2
Terminal Connection TypeFront
Data Sheet, Technical Information1SDC210032D0204
Declaration of Conformity - CE9AKK106713A5518
Wiring Diagram1SDM000067R0001
Instructions and Manuals1SDH000718R0001