AurFort
ABBXT2NABB XT2N 160 Ekip Dip LS/I In=160A 3p F F, manufacturer catalog image

ABB catalog image for this SKU; may represent the product family.

POWER CIRCUIT-BREAKER FOR TRAFO/GENERATOR/INSTALLATION PROTECTION

XT2N 160 Ekip Dip LS/I In=160A 3p F F

SKU 1SDA067058R1

ABB XT2N 160 Ekip Dip LS/I In=160A 3p F F: Power circuit-breaker for trafo/generator/installation protection. Rated current: 160 A. Pole configuration: 3P.

160 ARated current
3PPoles
XT2NProduct range
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 15, 2026.

1SDA067058R1 — selected manufacturer specifications
Product ID1SDA067058R1
Catalog DescriptionXT2N 160 Ekip Dip LS/I In=160A 3p F F
Country of OriginIndia
Made To OrderNo
Warranty ReturnProduct under warranty must be returned
Product Sales StatusActive
Quote OnlyNo
Stocked At WarehousesINABB015EXPU
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetUL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions9AKK108468A2349
Environmental Product Declaration - EPD9AKK108469A1855 9AKK108468A1897
Extended Product LifetimeProduct is Modular
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration9AKK108466A1425
RoHS Declaration9AKK108466A1424
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
Toxic Substances Control Act - TSCA9AKK108467A8326
Environmental Information9AKK108467A6707
Order Code US and CanadaXT2NE3160EFF000XXX
E-Number (Finland)3638188
E-Number (Norway)4309651
E-Number (Sweden)3182027
Minimum Order Quantity1 piece
Customs Tariff Number85362090
Product Net Width90 mm
Product Net Height130 mm
Product Net Depth / Length82.5 mm
Product Net Weight1.4 kg
Package Level 1 Unitsbox 1 piece
Package Level 1 Width130 mm
Package Level 1 Height208 mm
Package Level 1 Depth / Length145 mm
Package Level 1 Gross Weight1.71 kg
Package Level 1 EAN8015644007959
Brand / LabelABB
Circuit Breaker Type to be AssociatedPower Distribution
Product Main TypeSACE Tmax XT
Product NameMoulded Case Circuit Breaker
Product TypeAutomatic Circuit Breaker
VersionF
CAD Dimensional Drawing1SDH002230A1001
Connecting Capacity Main CircuitBusbar 32.5..100 mm²
Current TypeAC
Electrical Durability120 cycles per hour 8000 cycle
Mechanical Durability240 cycles per hour 25000 cycle
Number of Poles3P
Opening TimeCB with SOR 30 ms CB with UVR 30 ms
Order Multiple1 piece
Power Lossat Rated Operating Conditions per Pole 10.8 W
Rated Current (In)160 A
Rated Frequency (f)50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)8 kV
Rated Insulation Voltage (Ui)1000 V
Rated Operational Voltage690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
Rated Uninterrupted Current (Iu)160 A
Rated Voltage (Ur)690 V
Recommended Screw DriverMain Circuit M6
ReleaseEkip Dip LS/I
Release TypeEL
Short-Circuit Performance LevelN
StandardsIEC60947-2
Sub-typeXT2
Terminal Connection TypeFront
Terminal TypeBolt
Tightening Torque6 N·m
ABS Certificate1SDL000163R0109
ATEX CertificateNo certification needed
BV Certificate1SDL000163R0099
CB Certificate9AKK106713A2843
CQC CertificateCQC2013010307643219 CQC2013010307650258 CQC2018010307082330
Data Sheet, Technical InformationSDC210100D0206 1SDC210099D0206
Declaration of Conformity - CCC9AKK108466A7755 2020980307003311 2020980307003400
Declaration of Conformity - CE9AKK106713A5901
DNV GL Certificate1SDL000163R0096
EAC Certificate9AKK10103A1027
EU Data Act Compliance Declaration1SDH002560A1001
GL Certificate1SDL000163R0093
LR Certificate1SDL000163R0100
RINA Certificate1SDL000163R0098
UL Certificate1SDL000163R0112
VDE CertificateNo certification needed
Dimension Diagram1SDH000721R0100
Mechanical Drawings1SDH000721R0100
Wiring Diagram1SDM000068R0001
Instructions and Manuals1SDH000721R0001
IDEA Granular Category Code (IGCC)4932 >> 3 Pole Non-Interchangeable Trip Electronic Circuit Breakers

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.