AurFort
ABBXT4NABB XT4N 250 Ekip Dip LS/I In=250A 4p F F, manufacturer catalog image

ABB catalog image for this SKU; may represent the product family.

POWER CIRCUIT-BREAKER FOR TRAFO/GENERATOR/INSTALLATION PROTECTION

XT4N 250 Ekip Dip LS/I In=250A 4p F F

SKU 1SDA068147R1

ABB XT4N 250 Ekip Dip LS/I In=250A 4p F F: Power circuit-breaker for trafo/generator/installation protection. Rated current: 250 A. Pole configuration: 4P.

250 ARated current
4PPoles
XT4NProduct range
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 16, 2026.

1SDA068147R1 — selected manufacturer specifications
Product ID1SDA068147R1
Catalog DescriptionXT4N 250 Ekip Dip LS/I In=250A 4p F F
Country of OriginIndia
Made To OrderNo
Warranty ReturnProduct under warranty must be returned
Product Sales StatusActive
Quote OnlyNo
Stocked At WarehousesINABB015EXPU
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetUL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions9AKK108468A2352
Environmental Product Declaration - EPD9AKK108469A1858 9AKK108468A1898
Extended Product LifetimeProduct is Modular
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 56.30 %
REACH Declaration9AKK108466A1425
RoHS Declaration9AKK108466A1424
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
Toxic Substances Control Act - TSCA9AKK108467A8326
Environmental Information9AKK108467A6707
Order Code US and CanadaXT4NE4250EFF000XXX
E-Number (Finland)3641041
E-Number (Norway)4309768
E-Number (Sweden)3182051
Minimum Order Quantity1 piece
Customs Tariff Number85362090
Product Net Width140 mm
Product Net Height160 mm
Product Net Depth / Length82.5 mm
Product Net Weight2.931 kg
Package Level 1 Unitsbox 1 piece
Package Level 1 Width151 mm
Package Level 1 Height214 mm
Package Level 1 Depth / Length171 mm
Package Level 1 Gross Weight3.085 kg
Package Level 1 EAN8015644020446
Circuit Breaker Type to be AssociatedPower Distribution
Product Main TypeSACE Tmax XT
Product NameMoulded Case Circuit Breaker
Product TypeAutomatic Circuit Breaker
VersionF
CAD Dimensional Drawing1SDH001295R0677
Connecting Capacity Main CircuitBusbar 85..200 mm²
Current TypeAC
Electrical Durability120 cycles per hour 8000 cycle
Mechanical Durability240 cycles per hour 25000 cycle
Number of Poles4P
Opening TimeCB with SOR 30 ms CB with UVR 30 ms
Order Multiple1 piece
Power Lossat Rated Operating Conditions per Pole 16.4 W
Rated Current (In)250 A
Rated Frequency (f)50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)8 kV
Rated Insulation Voltage (Ui)1000 V
Rated Operational Voltage690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
Rated Uninterrupted Current (Iu)250 A
Rated Voltage (Ur)690 V
Recommended Screw DriverMain Circuit M8
ReleaseEkip Dip LS/I
Release TypeEL
Short-Circuit Performance LevelN
StandardsIEC60947-2
Sub-typeXT4
Terminal Connection TypeFront
Terminal TypeBolt
Tightening Torque8 N·m
ATEX CertificateNo certification needed
Data Sheet, Technical InformationSDC210100D0206 1SDC210099D0206
Declaration of Conformity - CE9AKK106713A5529
EU Data Act Compliance Declaration1SDH002560A1001
GL Certificate1SDL000163R0095
LR Certificate1SDL000163R0100
UL CertificateNo certification needed
VDE CertificateNo certification needed
Dimension Diagram1SDH000722R0100
Mechanical Drawings1SDH000722R0100
Wiring Diagram1SDM000068R0001
Instructions and Manuals1SDH000722R0001

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.