ABBXT4S

ABB catalog image for this SKU; may represent the product family.
POWER CIRCUIT-BREAKER FOR TRAFO/GENERATOR/INSTALLATION PROTECTION
XT4S 250 Ekip M Dip I In=250A 3p F F
SKU 1SDA068480R1ABB XT4S 250 Ekip M Dip I In=250A 3p F F: Power circuit-breaker for trafo/generator/installation protection. Rated current: 250 A. Pole configuration: 3P.
250 ARated current
3PPoles
XT4SProduct range
PRODUCT DATA
Technical specifications
Source: ABB English regional product catalog.
Verified September 16, 2026.
| Product ID | 1SDA068480R1 |
|---|---|
| Catalog Description | XT4S 250 Ekip M Dip I In=250A 3p F F |
| Country of Origin | India |
| Made To Order | No |
| Warranty Return | Product under warranty must be returned |
| Product Sales Status | Active |
| Quote Only | No |
| Stocked At Warehouses | INABB015EXPU |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2352 |
| Environmental Product Declaration - EPD | 9AKK108469A1858 9AKK108468A1898 |
| Extended Product Lifetime | Product is Modular |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 56.30 % |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| Environmental Information | 9AKK108467A6707 |
| Order Code US and Canada | XT4SE3250JFF000XXX |
| E-Number (Norway) | 4379953 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Product Net Width | 105 mm |
| Product Net Height | 160 mm |
| Product Net Depth / Length | 82.5 mm |
| Product Net Weight | 2.321 kg |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 151 mm |
| Package Level 1 Height | 214 mm |
| Package Level 1 Depth / Length | 171 mm |
| Package Level 1 Gross Weight | 2.443 kg |
| Package Level 1 EAN | 8015644023867 |
| Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH002230A1003 |
| Connecting Capacity Main Circuit | Busbar 85..200 mm² |
| Current Type | AC |
| Electrical Durability | 120 cycles per hour 8000 cycle |
| Mechanical Durability | 240 cycles per hour 25000 cycle |
| Number of Poles | 3P |
| Opening Time | CB with SOR 30 ms CB with UVR 30 ms |
| Order Multiple | 1 piece |
| Power Loss | at Rated Operating Conditions per Pole 16.4 W |
| Rated Current (In) | 250 A |
| Rated Frequency (f) | 50 / 60 Hz |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA |
| Rated Uninterrupted Current (Iu) | 250 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | Main Circuit M8 |
| Release | Ekip M Dip I |
| Release Type | EL |
| Short-Circuit Performance Level | S |
| Standards | IEC60947-2 |
| Sub-type | XT4 |
| Terminal Connection Type | Front |
| Terminal Type | Bolt |
| Tightening Torque | 8 N·m |
| ATEX Certificate | No certification needed |
| Data Sheet, Technical Information | SDC210100D0206 1SDC210099D0206 |
| Declaration of Conformity - CE | 9AKK106713A5529 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| GL Certificate | 1SDL000163R0095 |
| LR Certificate | 1SDL000163R0100 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Dimension Diagram | 1SDH000722R0100 |
| Mechanical Drawings | 1SDH000722R0100 |
| Wiring Diagram | 1SDM000068R0001 |
| Instructions and Manuals | 1SDH000722R0001 |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.