ABBSACE Emax 2

Representative ABB Emax 2 family image extracted from the manufacturer catalog. Frame, rating and configuration may differ; use the SKU and technical table to identify the listed package.
AIR CIRCUIT BREAKER WITH MEASURING PACKAGE
E2.2N 2500 A Ekip Touch LSI 3P Fixed + Measuring Package
SKU 1SDA071065R1MPABB E2.2N, 2500 A, 3-pole fixed air circuit breaker listed with Ekip Touch LSI protection and a measuring package. Rated ultimate short-circuit breaking capacity: 66 kA at 415 V AC.
2500 ARated current
3PPoles
66 kAIcu at 415 V AC
PRODUCT DATA
Technical specifications
Source: ABB February 2026 catalog (specifications translated into English).
Verified September 08, 2026.
| Product ID | 1SDA071065R1MP |
|---|---|
| Product range | SACE Emax 2 |
| Frame and performance level | E2.2N |
| Rated Current (In) | 2500 A |
| Number of Poles | 3P |
| Construction | Fixed |
| Trip Unit | Ekip Touch |
| Protection Functions | LSI |
| Package | Measuring package |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | 66 kA at 415 V AC |
| Measurement functions | Phase-to-phase and phase-to-neutral voltage; active, reactive and apparent power and energy; phase sequence; frequency; power factor; peak factor |
| Catalog reference | ABB Electrification Price List, February 2026, page 154 |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.