AurFort
ABBXT6SABB XT6S 1000 Ekip Dip LS/I In=1000 4p F F, manufacturer catalog image

ABB catalog image for this SKU; may represent the product family.

POWER CIRCUIT-BREAKER FOR TRAFO/GENERATOR/INSTALLATION PROTECTION

XT6S 1000 Ekip Dip LS/I In=1000 4p F F

SKU 1SDA100755R1

ABB XT6S 1000 Ekip Dip LS/I In=1000 4p F F: Power circuit-breaker for trafo/generator/installation protection. Rated current: 1000 A. Pole configuration: 4P.

1000 ARated current
4PPoles
XT6SProduct range
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 16, 2026.

1SDA100755R1 — selected manufacturer specifications
Product ID1SDA100755R1
Catalog DescriptionXT6S 1000 Ekip Dip LS/I In=1000 4p F F
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetUL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions9AKK108468A2356
Environmental Product Declaration - EPD9AKK108468A9752 9AKK108468A2295
Extended Product LifetimeProduct is Modular
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 60 %
REACH Declaration9AKK108466A1425
RoHS Declaration9AKK108466A1424
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
Toxic Substances Control Act - TSCA9AKK108467A8326
Environmental Information9AKK108467A6707
Order Code US and CanadaXT6SE41K0EFF000XXX
E-Number (Norway)4380584
Minimum Order Quantity1 piece
Customs Tariff Number85362090
Product Net Width280 mm
Product Net Height268 mm
Product Net Depth / Length103.5 mm
Product Net Weight12 kg
Package Level 1 Unitsbox 1 piece
Package Level 1 Width305 mm
Package Level 1 Height285 mm
Package Level 1 Depth / Length370 mm
Package Level 1 Gross Weight14 kg
Package Level 1 EAN8056221008099
Circuit Breaker Type to be AssociatedPower Distribution
Product Main TypeSACE Tmax XT
Product NameMoulded Case Circuit Breaker
Product TypeAutomatic Circuit Breaker
VersionF
CAD Dimensional Drawing1SDH002065A1214 1SDH002065A1245
Current TypeAC
Electrical Durability5000 cycle 60 cycles per hour
Mechanical Durability20000 cycle 120 cycles per hour
Number of Poles4P
Order Multiple1 piece
Power Loss83.5 W
Rated Current (In)1000 A
Rated Impulse Withstand Voltage (Uimp)8 kV
Rated Insulation Voltage (Ui)1000 V
Rated Operational Voltage690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 45 kA (500 V AC) 35 kA (525 V AC) 35 kA (690 V AC) 22 kA
Rated Short-time Withstand Current Low Voltage (Icw)10 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 45 kA (500 V AC) 35 kA (525 V AC) 35 kA (690 V AC) 22 kA
Rated Uninterrupted Current (Iu)1000 A
ReleaseEkip Dip LS/I
Release TypeEL
Short-Circuit Performance LevelS
StandardsIEC60947-2
Sub-typeXT6
Terminal Connection TypeFront
Data Sheet, Technical Information1SDC210100D0206 1SDC210099D0206
Declaration of Conformity - CE9AKK107680A2825
EU Data Act Compliance Declaration1SDH002560A1001
Mechanical Drawings1SDH002012A1101
Wiring Diagram1SDM000005A1001
Instructions and Manuals1SDH002012A1001

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.