POWER CIRCUIT-BREAKER FOR TRAFO/GENERATOR/INSTALLATION PROTECTION

XT6H 800 TMA 800-8000 3p F F

SKU 1SDA100762R1

ABB XT6H 800 TMA 800-8000 3p F F: Power circuit-breaker for trafo/generator/installation protection. Rated current: 800 A. Pole configuration: 3P.

800 ARated current
3PPoles
XT6HProduct range
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 15, 2026.

1SDA100762R1 — selected manufacturer specifications
Product ID1SDA100762R1
Catalog DescriptionXT6H 800 TMA 800-8000 3p F F
Country of OriginIndia
Made To OrderNo
Warranty ReturnProduct under warranty must be returned
Product Sales StatusActive
Quote OnlyNo
Stocked At WarehousesINABB015EXPU
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetUL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions9AKK108468A2355
Environmental Product Declaration - EPD9AKK108468A9751 9AKK108468A1894
Extended Product LifetimeProduct is Modular
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 60 %
REACH Declaration9AKK108466A1425
RoHS Declaration9AKK108466A1424
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
Toxic Substances Control Act - TSCA9AKK108467A8326
Environmental Information9AKK108467A6707
Order Code US and CanadaXT6HE3800BFF000XXX
E-Number (Norway)4380509
Minimum Order Quantity1 piece
Customs Tariff Number85362090
Product Net Width210 mm
Product Net Height268 mm
Product Net Depth / Length103.5 mm
Product Net Weight9.5 kg
Package Level 1 Unitsbox 1 piece
Package Level 1 Width305 mm
Package Level 1 Height285 mm
Package Level 1 Depth / Length370 mm
Package Level 1 Gross Weight9.6 kg
Package Level 1 EAN8056221008167
Circuit Breaker Type to be AssociatedPower Distribution
Product Main TypeSACE Tmax XT
Product NameMoulded Case Circuit Breaker
Product TypeAutomatic Circuit Breaker
VersionF
CAD Dimensional Drawing1SDH002065A1190 1SDH002065A1245
Current TypeAC/DC
Electrical Durability5000 cycle 60 cycles per hour
Mechanical Durability20000 cycle 120 cycles per hour
Number of Poles3P
Order Multiple1 piece
Power Loss54.2 W
Rated Current (In)800 A
Rated Impulse Withstand Voltage (Uimp)8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)4000…8000 A
Rated Insulation Voltage (Ui)1000 V
Rated Operational Voltage690 V AC 750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 100 kA (230 V AC) 100 kA (240 V AC) 100 kA (380 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 50 kA (500 V AC) 50 kA (525 V AC) 50 kA (690 V AC) 25 kA (250 V DC) 2 Poles in Series 35 kA (500 V DC) 2 Poles in Series 25 kA (750 V DC) 3 Poles in Series 18 kA
Rated Short-time Withstand Current Low Voltage (Icw)10 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(220 V AC) 100 kA (230 V AC) 100 kA (240 V AC) 100 kA (380 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 50 kA (500 V AC) 50 kA (525 V AC) 50 kA (690 V AC) 25 kA (250 V DC) 2 Poles in Series 70 kA (500 V DC) 2 Poles in Series 50 kA (750 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)800 A
ReleaseTMA
Release TypeTM
Setting Range560…800 A
Short-Circuit Performance LevelH
StandardsIEC60947-2
Sub-typeXT6
Terminal Connection TypeFront
Data Sheet, Technical Information1SDC210100D0206 1SDC210099D0206
Declaration of Conformity - CE9AKK107680A2825
Mechanical Drawings1SDH002012A1101
Wiring Diagram1SDM000005A1001
Instructions and Manuals1SDH002012A1001

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.