PRODUCT DATA
Technical specifications
Source: ABB English regional product catalog.
Verified September 09, 2026.
| Global Commercial Alias | PSE250-600-70-1 |
|---|---|
| Product ID | 1SFA897113R7001 |
| ABB Type Designation | PSE250-600-70-1 |
| Catalog Description | PSE250-600-70-1 Softstarter - 250 A - 208 ... 600 V AC |
| Configuration Only | No |
| Country of Origin | Sweden China India |
| Criticality | No |
| Lead Time | 1 day 0 day |
| Made To Order | No |
| Note | No |
| Product Availability Class | Only for warranty purposes. Not available for normal sales |
| Product Sales Status | Active |
| Quote Only | No |
| Stocked At Warehouses | BRAPR001EXPU CHNOR001EXPU CLABB001EXPU CSB WMSACNURMQ CNIAB001EXPU COABB001EXPU DEAPRMLCEXPU DKSER001EXPU DUABB001EXPU DUABB003EXPU EESER001EXPU EGAUT001EXPU ESATD001EXPU FISER001EXPU FRAUT001EXPU GBINS001EXPU GRABB001EXPU INABB015EXPU INABB039EXPU INABBRLCEXPU ITIND002EXPU NLABB021EXPU NOATDRLCEXPU SGIND002EXPU TRDMD001EXPU USABB251EXPU ZATAD021EXPU |
| Storage Location | 4014 |
| Warranty Return | Product under warranty must be returned |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85371091 |
| Data Sheet, Technical Information | 1SFC132012C0201 |
| Instructions and Manuals | 1SFC132427M0201 |
| Instructions and Manuals (Part 2) | 1SFC132057M0201 |
| Instructions and Manuals (Part 3) | 1SFC132060M0201 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| EPLAN Data | 9AAC170224_EPLAN |
| Wiring Diagram | N/A |
| Product Net Width | 190 mm |
| Product Net Height | 435 mm |
| Product Net Depth / Length | 237 mm |
| Product Net Weight | 10.6 kg |
| Rated Operational Voltage | 208 ... 600 V AC |
| Rated Control Supply Voltage (Us) | 100 ... 250 V AC |
| Rated Control Circuit Voltage (Uc) | 24 V DC |
| Rated Frequency (f) | 50/60 Hz Main Circuit 50 / 60 Hz |
| Rated Operational Power - In-Line Connection (Pe) | (230 V) 75 kW (400 V) 132 kW (500 V) 160 kW |
| Rated Operational Current - In-Line Connection (Ie) | 250 A |
| Service Factor Percentage | 100 % |
| Overload Protection | Built-in electronic overload protection |
| Integrated Electronic Overload | Yes |
| Starting Capacity at Maximum Rated Current Ie | 4xIe for 10s |
| Ramp Time | 0 ... 30 s 1 ... 30 s |
| Initial Voltage During Start | 30 ... 70 % |
| Step Down Voltage Special Ramp | No % |
| Current Limit Function | 1.5 ... 7xIe |
| Switch for Inside Delta Connection | No |
| Run Signal Relay | Yes |
| By-pass Signal Relay | Yes |
| Fault Signal Relay | Yes |
| Overload Signal Relay | Yes |
| Analog Outputs | 4…20 mA |
| Signal Indication Completed Start Ramp (LED) | Green |
| Signal Indication Ready to Start/Standby ON (LED) | Green |
| Signal Indication Running R (LED) | Green |
| Signal Indication Ramping Up/Down (LED) | Green |
| Signal Indication Protection (LED) | Yellow |
| Signal Indication Fault (LED) | Red |
| Number of Starts Per Hour at 3.5*Ie for 7 sec. 50% ON Time 50% OFF Time | 10 |
| Communication | Modbus-RTU |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00 |
| Terminal Type | Main Circuit: Bars |
| Connecting Capacity Main Circuit | Hole Diameter 8.5 mm Rigid 1/2 x 2.5 ... 70 mm² Width and Thickness 17.5x5 mm |
| Connecting Capacity Control Circuit | Rigid 1 x 2.5 mm² Rigid 2 x 1.5 mm² |
| Connecting Capacity Supply Circuit | Rigid 1 x 2.5 |
| Tightening Torque | Control Circuit 0.5 N·m Main Circuit 28 N·m Supply Circuit 0.5 N·m |
| Product Main Type | PSE250 |
| Function | Soft start with torque control Soft start with voltage ramp Soft stop with torque control Soft stop with voltage ramp Kick start Sequence start Current limit Start reverse (external contactors) Automatic restart Event log |
| Protection Function | Electronic overload protection, EOL; Locked rotor protection; Current underload protection |
| Horsepower Rating UL/CSA | (200 ... 208 V AC) Three Phase 75 Hp (220 ... 240 V AC) Three Phase 100 Hp (440 ... 480 V AC) Three Phase 200 Hp (550 ... 600 V AC) Three Phase 250 Hp |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| Tightening Torque UL/CSA | Control Circuit 4.4 in·lb Main Circuit 247.8 Supply Circuit 4.4 in·lb |
| Ambient Air Temperature | Operation -25 ... +60 °C Storage -40 ... +70 °C |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2022-006481 |
| RoHS Declaration | 2CMT2022-006500 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006524 |
| Environmental Product Declaration - EPD | 1SFC132476D0201 |
| CQC Certificate | CQC2018010304109915 |
| Declaration of Conformity - CCC | 2020980304001510 |
| Declaration of Conformity - CE | 2CMT2015-005447 |
| DNV Certificate | 1SFC132383M0001 | TAE0000342 |
| EU Data Act Compliance Declaration | 1SFC132495M0201 |
| Package Level 1 Width | 261 mm |
| Package Level 1 Depth / Length | 325 mm |
| Package Level 1 Height | 510 mm |
| Package Level 1 Gross Weight | 13.3 kg |
| Package Level 1 EAN | 7320500515037 |
| Package Level 1 Units | box 1 piece |
| IDEA Granular Category Code (IGCC) | 4740 >> Soft starter |