AurFort
ABBPSTX30-600-70ABB PSTX30-600-70, manufacturer catalog image

ABB catalog image for this SKU; may represent the product family.

SOFT STARTER

PSTX30-600-70

SKU 1SFA898103R7000

ABB PSTX30-600-70: Soft starter.

PSTX30-600-70Product range
Soft starterProduct type
1SFA898103R7000Reference
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 09, 2026.

1SFA898103R7000 — selected manufacturer specifications
Global Commercial AliasPSTX30-600-70
Product ID1SFA898103R7000
ABB Type DesignationPSTX30-600-70
Catalog DescriptionPSTX30-600-70 Softstarter - 30 A - 208 ... 600 V AC
Country of OriginSweden China
Lead Time0 day 28 day 2 week
Made To OrderNo Yes
Warranty ReturnProduct under warranty must be returned
Product Sales StatusActive Inactive
Quote OnlyNo
Stocked At WarehousesAETAD009EXPU BRABB008EXPU BRAPR001EXPU CHNOR001EXPU CHSEC006EXPU CLABB001EXPU CSB WMSACNURMQ CNIAB001EXPU COABB001EXPU CZABB006EXPU DEAPRMLCEXPU DKSER001EXPU DUABB001EXPU DUABB003EXPU EESER001EXPU EGAUT001EXPU ESATD001EXPU FISER001EXPU FRAUT001EXPU GBINS001EXPU GRABB001EXPU INABB039EXPU INABBRLCEXPU ITIND002EXPU NLABB021EXPU NOATDRLCEXPU SGIND002EXPU TRDMD001EXPU USABB251EXPU ZATAD021EXPU
Configuration OnlyNo
CriticalityNo
NoteNo
Product Availability ClassOnly for warranty purposes. Not available for normal sales
Storage Location4014
Minimum Order Quantity1 piece
Customs Tariff Number85371091
Data Sheet, Technical Information1SFC132012C0201
Instructions and Manuals1SFC132428M0201
Instructions and Manuals (Part 2)1SFC132081M0201
Instructions and Manuals (Part 3)1SFC132060M0201
CAD Dimensional Drawing2CDC001079B0201
EPLAN Data9AAC181159_EPLAN
Wiring DiagramN/A
Product Net Width150 mm
Product Net Height314 mm
Product Net Depth / Length198 mm
Product Net Weight4.6 kg
Rated Operational Voltage208 ... 600 V AC
Rated Control Supply Voltage (Us)100 ... 250 V AC
Rated Control Circuit Voltage (Uc)24 V DC
Rated Frequency (f)50/60 Hz Main Circuit 50 / 60 Hz
Rated Operational Power - In-Line Connection (Pe)(230 V) 7.5 kW (400 V) 15 kW (500 V) 18.5 kW
Rated Operational Current - In-Line Connection (Ie)30 A
Rated Operational Power - Inside Delta Connectionat 230 V 12.5 kW at 400 V 25 kW at 500 V 30 kW
Rated Operational Current - Inside Delta Connection52 A
Service Factor Percentage100 %
Overload ProtectionBuilt-in electronic overload protection
Integrated Electronic OverloadYes
Starting Capacity at Maximum Rated Current Ie4xIe for 10s
Ramp Time1 ... 120 s
Initial Voltage During Start10 ... 99 %
Step Down Voltage Special Ramp100 ... 10 %
Current Limit Function1.5 ... 7.5 xle
Switch for Inside Delta ConnectionYes
Run Signal RelayYes
By-pass Signal RelayYes
Fault Signal RelayYes
Overload Signal RelayYes
Analog Outputs0…10 V, 0…20 mA, 4…20 mA
Signal Indication Ready to Start/Standby ON (LED)Green
Signal Indication Running R (LED)Green
Signal Indication Protection (LED)Yellow
Signal Indication Fault (LED)Red
CommunicationModbus-RTU; Modbus-TCP; Ethernet-IP; EtherCAT; DeviceNet; CANopen; Profibus; Profinet; BACnet-IP; BACnet-MSTP
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal TypeCable Clamp
Connecting Capacity Main CircuitHole Diameter 8.5 mm
Connecting Capacity Control CircuitRigid 1 x 2.5 mm²
Connecting Capacity Supply CircuitRigid 1 x 2.5
Tightening TorqueMain Circuit 8 N·m
Product Main TypePSTX30
FunctionAuto phase sequence detection Automatic restart Current limit Current limit ramp Dual current limit Dynamic brake Electricity metering Electronic overload Time-to-cool Emergency mode Event log Full voltage start Jog with slow speed, forward and reverse Keypad password Kick start Limp mode with two-phase motor control if one set of thyristors is shorted Motor heating Pre-start function Pump cleaning Real time clock Sequence start Soft start with torque control Soft start with voltage ramp Soft stop with torque control Soft stop with voltage ramp Stand still brake Start reverse (external contactors) Thyristor runtime measurement Torque limit Voltage sags detection
Protection FunctionBypass open protection; Current imbalance protection; Current underload protection; Dual overload (separate overload for start and run); Earth fault protection / ground fault protection; Electronic overload protection, EOL; Extension IO failure protection; Fieldbus failure protection; HMI failure protection; Locked rotor protection; Max number of starts/hour; Over voltage protection; Phase reversal protection; Power factor underload protection; PT-100 connection; PTC connection; Too long current limit protection; Too long start time protection; Under voltage protection; User defined protection; Voltage imbalance protection
Warning DetailsCurrent imbalance warning; Current underload warning; Electronic overload Time-to-trip; EOL warning; Faulty fan warning; Locked rotor warning; Motor runtime limit warning; Over voltage warning; Phase loss warning (for standby); Power factor underload warning; Short circuit warning (for Limp mode); THD(U) - Total Harmonic Distortion warning; Thyristor overload warning (SCR); Under voltage warning; Voltage imbalance warning
Horsepower Rating UL/CSA(200 ... 208 V AC) Three Phase 7.5 Hp (220 ... 240 V AC) Three Phase 10 Hp (440 ... 480 V AC) Three Phase 20 Hp (550 ... 600 V AC) Three Phase 25 Hp
Maximum Operating Voltage UL/CSAMain Circuit 600 V
Tightening Torque UL/CSAMain Circuit 70.8
Ambient Air TemperatureOperation -25 ... +60 °C Storage -40 ... +70 °C
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration2CMT2022-006481
RoHS Declaration2CMT2022-006500
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA2CMT2023-006524
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetUL 2799 Zero Waste To Landfill Validation available
ABB EcoSolutions Profile1SFC100125C0367
End Of Life Disassembling Instructions1SFC132450M0201
Environmental Product Declaration - EPD1SFC132444 1SFC132435
Extended Product LifetimeProduct Durability is Enhanced
Improved Energy Efficiency for CustomersProduct Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 73.4 %
CQC CertificateCN: CQC2014010304744405 / SE: CQC2014010304724380
Declaration of Conformity - CCCCN: 2020980304001091 / SE: 2020980304001489
Declaration of Conformity - CE2CMT005209
DNV CertificateTAE000087N
EU Data Act Compliance Declaration1SFC132498M0201
Package Level 1 Width200 mm
Package Level 1 Depth / Length282 mm
Package Level 1 Height388 mm
Package Level 1 Gross Weight5.6 kg
Package Level 1 EAN7320500501290
Package Level 1 Unitsbox 1 piece
IDEA Granular Category Code (IGCC)4740 >> Soft starter

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.