ABBPSTX142-600-70

ABB catalog image for this SKU; may represent the product family.
SOFT STARTER
PSTX142-600-70
SKU 1SFA898110R7000ABB PSTX142-600-70: Soft starter.
PSTX142-600-70Product range
Soft starterProduct type
1SFA898110R7000Reference
PRODUCT DATA
Technical specifications
Source: ABB English regional product catalog.
Verified September 09, 2026.
| Global Commercial Alias | PSTX142-600-70 |
|---|---|
| Product ID | 1SFA898110R7000 |
| ABB Type Designation | PSTX142-600-70 |
| Catalog Description | PSTX142-600-70 Softstarter - 142 A - 208 ... 600 V AC |
| Country of Origin | Sweden China |
| Lead Time | 0 day 21 day 2 week |
| Made To Order | No Yes |
| Warranty Return | Product under warranty must be returned |
| Product Sales Status | Active Inactive |
| Quote Only | No |
| Stocked At Warehouses | AETAD009EXPU BRABB008EXPU BRAPR001EXPU CHNOR001EXPU CHSEC006EXPU CLABB001EXPU CSB WMSACNURMQ CNIAB001EXPU COABB001EXPU CZABB006EXPU DEAPRMLCEXPU DKSER001EXPU DUABB001EXPU DUABB003EXPU EESER001EXPU EGAUT001EXPU ESATD001EXPU FISER001EXPU FRAUT001EXPU GBINS001EXPU GRABB001EXPU INABB039EXPU INABBRLCEXPU ITIND002EXPU NLABB021EXPU NOATDRLCEXPU SGIND002EXPU TRDMD001EXPU USABB251EXPU ZATAD021EXPU |
| Configuration Only | No |
| Criticality | No |
| Note | No |
| Product Availability Class | Only for warranty purposes. Not available for normal sales |
| Storage Location | 4014 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85371091 |
| Data Sheet, Technical Information | 1SFC132012C0201 |
| Instructions and Manuals | 1SFC132428M0201 |
| Instructions and Manuals (Part 2) | 1SFC132081M0201 |
| Instructions and Manuals (Part 3) | 1SFC132060M0201 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| EPLAN Data | 9AAC181166_EPLAN |
| Wiring Diagram | N/A |
| Product Net Width | 199 mm |
| Product Net Height | 377 mm |
| Product Net Depth / Length | 283.3 mm |
| Product Net Weight | 7 kg |
| Rated Operational Voltage | 208 ... 600 V AC |
| Rated Control Supply Voltage (Us) | 100 ... 250 V AC |
| Rated Control Circuit Voltage (Uc) | 24 V DC |
| Rated Frequency (f) | 50/60 Hz Main Circuit 50 / 60 Hz |
| Rated Operational Power - In-Line Connection (Pe) | (230 V) 37 kW (400 V) 75 kW (500 V) 90 kW |
| Rated Operational Current - In-Line Connection (Ie) | 142 A |
| Rated Operational Power - Inside Delta Connection | at 230 V 75 kW at 400 V 132 kW at 500 V 160 kW |
| Rated Operational Current - Inside Delta Connection | 245 A |
| Service Factor Percentage | 100 % |
| Overload Protection | Built-in electronic overload protection |
| Integrated Electronic Overload | Yes |
| Starting Capacity at Maximum Rated Current Ie | 4xIe for 10s |
| Ramp Time | 1 ... 120 s |
| Initial Voltage During Start | 10 ... 99 % |
| Step Down Voltage Special Ramp | 100 ... 10 % |
| Current Limit Function | 1.5 ... 7.5 xle |
| Switch for Inside Delta Connection | Yes |
| Run Signal Relay | Yes |
| By-pass Signal Relay | Yes |
| Fault Signal Relay | Yes |
| Overload Signal Relay | Yes |
| Analog Outputs | 0…10 V, 0…20 mA, 4…20 mA |
| Signal Indication Ready to Start/Standby ON (LED) | Green |
| Signal Indication Running R (LED) | Green |
| Signal Indication Protection (LED) | Yellow |
| Signal Indication Fault (LED) | Red |
| Communication | Modbus-RTU; Modbus-TCP; Ethernet-IP; EtherCAT; DeviceNet; CANopen; Profibus; Profinet; BACnet-IP; BACnet-MSTP |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00 |
| Terminal Type | Main Circuit: Bars |
| Connecting Capacity Main Circuit | Hole Diameter 8.5 mm |
| Connecting Capacity Control Circuit | Rigid 1 x 2.5 mm² |
| Connecting Capacity Supply Circuit | Rigid 1 x 2.5 |
| Tightening Torque | Main Circuit 14 N·m |
| Product Main Type | PSTX142 |
| Function | Auto phase sequence detection Automatic restart Current limit Current limit ramp Dual current limit Dynamic brake Electricity metering Electronic overload Time-to-cool Emergency mode Event log Full voltage start Jog with slow speed, forward and reverse Keypad password Kick start Limp mode with two-phase motor control if one set of thyristors is shorted Motor heating Pre-start function Pump cleaning Real time clock Sequence start Soft start with torque control Soft start with voltage ramp Soft stop with torque control Soft stop with voltage ramp Stand still brake Start reverse (external contactors) Thyristor runtime measurement Torque limit Voltage sags detection |
| Protection Function | Bypass open protection; Current imbalance protection; Current underload protection; Dual overload (separate overload for start and run); Earth fault protection / ground fault protection; Electronic overload protection, EOL; Extension IO failure protection; Fieldbus failure protection; HMI failure protection; Locked rotor protection; Max number of starts/hour; Over voltage protection; Phase reversal protection; Power factor underload protection; PT-100 connection; PTC connection; Too long current limit protection; Too long start time protection; Under voltage protection; User defined protection; Voltage imbalance protection |
| Warning Details | Current imbalance warning; Current underload warning; Electronic overload Time-to-trip; EOL warning; Faulty fan warning; Locked rotor warning; Motor runtime limit warning; Over voltage warning; Phase loss warning (for standby); Power factor underload warning; Short circuit warning (for Limp mode); THD(U) - Total Harmonic Distortion warning; Thyristor overload warning (SCR); Under voltage warning; Voltage imbalance warning |
| Horsepower Rating UL/CSA | (200 ... 208 V AC) Three Phase 40 Hp (220 ... 240 V AC) Three Phase 50 Hp (440 ... 480 V AC) Three Phase 100 Hp (550 ... 600 V AC) Three Phase 125 Hp |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| Tightening Torque UL/CSA | Main Circuit 123.9 |
| Ambient Air Temperature | Operation -25 ... +60 °C Storage -40 ... +70 °C |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2022-006481 |
| RoHS Declaration | 2CMT2022-006500 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006524 |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| ABB EcoSolutions Profile | 1SFC100125C0367 |
| End Of Life Disassembling Instructions | 1SFC132451M0201 |
| Environmental Product Declaration - EPD | 1SFC132445 1SFC132436 |
| Extended Product Lifetime | Product Durability is Enhanced |
| Improved Energy Efficiency for Customers | Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 74.8 % |
| CQC Certificate | CN: CQC2014010304744407 / SE: CQC2014010304724379 |
| Declaration of Conformity - CCC | CN: 2020980304001092 / SE: 2020980304001485 |
| Declaration of Conformity - CE | 2CMT005209 |
| DNV Certificate | TAE000087N |
| EU Data Act Compliance Declaration | 1SFC132498M0201 |
| Package Level 1 Width | 263 mm |
| Package Level 1 Depth / Length | 323 mm |
| Package Level 1 Height | 454 mm |
| Package Level 1 Gross Weight | 8.7 kg |
| Package Level 1 EAN | 7320500501467 |
| Package Level 1 Units | box 1 piece |
| IDEA Granular Category Code (IGCC) | 4740 >> Soft starter |