AurFort
ABBCP-C.1ABB CP-C.1 24/20.0, manufacturer catalog image

ABB catalog image for this SKU; may represent the product family.

DC-POWER SUPPLY

CP-C.1 24/20.0

SKU 1SVR360763R1001

ABB CP-C.1 24/20.0: DC-power supply.

CP-C.1Product range
DC-power supplyProduct type
1SVR360763R1001Reference
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 09, 2026.

1SVR360763R1001 — selected manufacturer specifications
Product ID1SVR360763R1001
Catalog DescriptionCP-C.1 24/20.0 Power supply In:100-240VAC/90-300VDC Out:DC 24V/20A
Country of OriginChina India
Lead Time95 day
Made To OrderNo
Warranty ReturnProduct under warranty must be returned
Product Sales StatusInactive Active
Quote OnlyNo
Stocked At WarehousesINABB015EXPU
Minimum Order Quantity1 piece
Customs Tariff Number85044095
Data Sheet, Technical Information2CDC114106D0201
Instructions and Manuals1SVC360560M0000
Product Net Width82 mm
Product Net Height129.4 mm
Product Net Depth / Length136 mm
Product Net Weight1.57 kg
Package Level 1 Width110 mm
Package Level 1 Depth / Length168 mm
Package Level 1 Height160 mm
Package Level 1 Gross Weight1.7 kg
Package Level 1 EAN4013614503832
Package Level 1 Unitsbox 1 piece
FunctionSwitch mode power supply
Number of Phases1-phase
Rated Input Voltage (UIN)100 ... 240 V AC 100 ... 270 V DC
Input Voltage (Uin)85 ... 264 V AC 90 ... 300 V DC
Typical Input Current(115 V AC) 4.6 A (230 V AC) 2.3 A
Hold-up Time(230 V AC) min. 40 ms
Rated Frequency (f)50 / 60 Hz
Rated Frequency Limits45 ... 65 Hz
Characteristic of OutputU/I Characteristic Curve with Power Reserve
Rated Output Power480 W
Output Power480 W
Rated Output Voltage24 V DC
Output Voltage (Uout)24 V DC 22.5 ... 28.5 V DC
Rated Output Current-25 °C ... +40 °C 26 A -25 °C ... +60 °C 20 A
Output Current20 A
Output Current Maximum (Iout)26 A
Rated Impulse Withstand Voltage (Uimp)Input Circuit / Output Circuit 4 kV Input Circuit / PE 4 kV Input Circuit / Relay Contact 4 kV Output Circuit / PE 0.5 kV Output Circuit 0.5 kV
Rated Insulation Voltage (Ui)Input Circuit / Output Circuit 300 V Input Circuit / PE 300 V Input Circuit / Relay Contact 300 V Output Circuit / PE 50 V
Degree of ProtectionHousing IP20 Terminals IP20
Pollution Degree2
Connecting Capacity Input CircuitFlexible with Ferrule 0.5 ... 2.5 mm² Flexible 0.5 ... 2.5 mm² Rigid 0.5 ... 4 mm²
Connecting Capacity Output CircuitFlexible with Ferrule 2.5 ... 10 mm² Flexible 2.5 ... 10 mm² Rigid 2.5 ... 16 mm²
Tightening TorqueAuxiliary Circuit 0.5 N·m Input Circuit 0.5 N·m Output Circuit 1.2 N·m
Wire Stripping LengthAuxiliary Circuit 8 mm Input Circuit 8 mm Output Circuit 10 mm
Recommended Screw DriverInput Circuit / Output Circuit PH1 Input Circuit / Output Circuit 0.8 x 4
Minimum Mounting DistanceElectrical Conductive Board, Horizontal 25 mm Electrical Conductive Board, Vertical 25 mm Other Device Same Type, Horizontal 25 mm Other Device Same Type, Vertical 25 mm
Mounting PositionPosition 1 7
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
StandardsCAN/CSA C22.2 No.107.1 IEC/EN 63000 IEC/EN 61000-6-2 IEC/EN 61000-6-3 IEC/EN 61204 UL 508 IEC/EN 61010-1 UL 61010-1 UL 61010-2-201
Connecting Capacity Input Circuit UL/CSAFlexible with Ferrule 20-12 AWG Flexible 20-12 AWG Rigid 20-10 AWG
Connecting Capacity Output Circuit UL/CSAFlexible 12-8 AWG Rigid 12-6 AWG
Tightening Torque UL/CSAInput Circuit 4.4 in·lb Output Circuit 10.5 in·lb
Electrostatic Discharge (ESD Immunity) acc. to IEC 61000-4-2Level 4 Air Discharge 15 kV Level 4 Contact Discharge 8 kV
Radiated Electromagnetic Field Immunity acc. to IEC 61000-4-3Level 3 10 V/m
Electrical Fast Transient (Burst Immunity) acc. to IEC 61000-4-4Level 4 Power Supply Port Signal 4 kV
Surge Immunity acc. to IEC 61000-4-5Level 4 Line-to-Ground 4 kV Level 4 Line-to-Line 2 kV
Conducted Disturbances Immunity acc. to IEC 61000-4-6Level 3 10 V
Electromagnetic Compatibility (EMC)Immunity - Class B Emission - Class B
Ambient Air TemperatureOperation -25 ... +70 °C Storage -40 ... +85 °C
Maximum Operating Altitude Permissible5000 m
Resistance to Damp Heat acc. to IEC 60068-2-30Test Db: 55°C, 2 cycles
Resistance to Shock acc. to IEC 60068-2-2730g 3 shocks 6 ms
Resistance to Vibrations±0.15 mm 10 ... 58 Hz 10 Sweep Cycles Each Axis: 2g 58 ... 150 Hz
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration1SVD982001-4501
RoHS Declaration1SVD982001-4401
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA2CMT2023-006535
ABS CertificateABS_17-HG1591548-2-PDA
CB CertificateCB_DK_103862_A2_UL
cULus CertificatecULus508_20161102-E174460
cURus CertificatecURus60950_E196145-A11-UL cURusANSI-12-12_20161122_E317914
Declaration of Conformity - CE1SVD982010-00
DNV GL CertificateDNV_GL_TAA00000YB_1
SEMI CertificateSEMI_F47_4787681819-2
E-Number (Finland)2712542
E-Number (Norway)6609455
E-Number (Sweden)5213181

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.