AurFort
ABBCP-DABB CP-D 24/0.42, manufacturer catalog image

ABB catalog image for this SKU; may represent the product family.

DC-POWER SUPPLY

CP-D 24/0.42

SKU 1SVR427041R0000

ABB CP-D 24/0.42: DC-power supply.

CP-DProduct range
DC-power supplyProduct type
1SVR427041R0000Reference
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 09, 2026.

1SVR427041R0000 — selected manufacturer specifications
Product ID1SVR427041R0000
Catalog DescriptionCP-D 24/0.42 Power supply In: 100-240VAC Out: 24VDC/0.42A
Country of OriginGermany China
Lead Time0 day 55 day 160 day
Made To OrderNo
Warranty ReturnProduct under warranty must be returned
Product Sales StatusActive Inactive
Quote OnlyNo
Stocked At WarehousesAETAD009EXPU BRABB008EXPU CHSEC006EXPU CZABB004EXPU
Minimum Order Quantity1 piece
Customs Tariff Number85044095
Data Sheet, Technical Information2CDC114054D0201
Instructions and Manuals1SVC427040M0001
Product Net Width18 mm
Product Net Height91 mm
Product Net Depth / Length57.5 mm
Product Net Weight0.066 kg
Package Level 1 Width91 mm
Package Level 1 Depth / Length134 mm
Package Level 1 Height34 mm
Package Level 1 Gross Weight0.111 kg
Package Level 1 EAN4016779661164
Package Level 1 Unitsbox 1 piece
FunctionSwitch mode power supply
Number of Phases1-phase
Rated Input Voltage (UIN)100 ... 240 V AC
Input Voltage (Uin)90 ... 264 V AC 120 ... 375 V DC
Rated Frequency (f)50 / 60 Hz
Rated Frequency Limits47 ... 63 Hz
Characteristic of OutputHiccup-Mode
Rated Output Power10 W
Output Power10 W
Rated Output Voltage24 V DC
Output Voltage (Uout)24 V DC
Rated Output Current0.42 A
Output Current0.42 A
Output Current Maximum (Iout)0.42 A
Rated Impulse Withstand Voltage (Uimp)Input Circuit / Output Circuit 3 kV
Rated Insulation Voltage (Ui)Input Circuit / Output Circuit 300 V Input Circuit / PE 300 V Output Circuit / PE 50 V
Degree of ProtectionHousing IP20 Terminals IP20
Pollution Degree2
Connecting Capacity Input CircuitFlexible with Ferrule 0.2 ... 1.5 mm² Rigid 0.2 ... 2.5 mm²
Connecting Capacity Output CircuitFlexible with Ferrule 0.2 .... 2.5 mm² Rigid 0.2 ... 2.5 mm²
Tightening TorqueInput Circuit 0.6 N·m Output Circuit 0.6 N·m
Wire Stripping LengthInput Circuit 4 mm Output Circuit 4 mm
Recommended Screw DriverPH1
Minimum Mounting DistanceElectrical Conductive Board, Horizontal 25 mm Electrical Conductive Board, Vertical 25 mm Other Device Same Type, Horizontal 25 mm Other Device Same Type, Vertical 25 mm
Mounting Position1
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
StandardsCAN/CSA C22.2 No.107.1 CAN/CSA C22.2 No.223 CAN/CSA C22.2 No.60950 IEC/EN 63000 IEC 60950-1 IEC/EN 61000-6-2 IEC/EN 61000-6-3 UL 1310 UL 508 UL 60950
Connecting Capacity Input Circuit UL/CSARigid 24-12 AWG
Connecting Capacity Output Circuit UL/CSARigid 24-12 AWG
Tightening Torque UL/CSAInput Circuit 5 in·lb Output Circuit 5 in·lb
Electrostatic Discharge (ESD Immunity) acc. to IEC 61000-4-2Level 4 Air Discharge 8 kV Level 4 Contact Discharge 4 kV
Radiated Electromagnetic Field Immunity acc. to IEC 61000-4-3Level 3 10 V/m
Electrical Fast Transient (Burst Immunity) acc. to IEC 61000-4-4Level 4 Power Supply Port Signal 4 kV
Surge Immunity acc. to IEC 61000-4-5Level 3 Line-to-Line 2 kV
Conducted Disturbances Immunity acc. to IEC 61000-4-6Level 3 10 V
Electromagnetic Compatibility (EMC)Emission - Class B Immunity - Class B
Ambient Air TemperatureOperation -40 ... +70 °C Storage -40 ... +85 °C
Maximum Operating Altitude Permissible4850 m
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration1SVD982001-4501
RoHS Declaration1SVD982001-4401
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA2CMT2023-006535
Environmental Product Declaration - EPDNo certification needed
cUL CertificatecUL508_E174460
cUR CertificatecUR60950_E196145 cUR1310_E313203
Declaration of Conformity - CE1SVD982007-00
TÜV CertificateTUV_EN62368_B_0442540019_20200925
UL CertificateUL508_E174460
UR CertificateUR60950_E196145 UR1310_E313203
E-Number (Finland)2712078
E-Number (Norway)6609492
E-Number (Sweden)5218726

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.