AurFort
ABBS300PABB S301P-C63, manufacturer catalog image

ABB catalog image for this SKU; may represent the product family.

MINIATURE CIRCUIT BREAKER

S301P-C63

SKU 2CDS381001R0634

ABB S301P-C63 is a miniature circuit breaker, rated at 63 A with a 1P configuration. Tripping characteristic: C.

63 ARated current
1PPoles
CTrip curve
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 07, 2026.

2CDS381001R0634 — selected manufacturer specifications
Product ID2CDS381001R0634
Catalog DescriptionMiniature Circuit Breaker - S300P - 1P - 63 A - C - (AC) 15 kA
Rated Current (In)63 A
Number of Poles1P
Number of Protected Poles1
Tripping CharacteristicC
Input Voltage TypeAC/DC
Rated Operational Voltageacc. to IEC 60898-1 240 V AC acc. to IEC 60947-2 240 V AC
Operational VoltageMaximum (Incl. Tolerance) 254 V AC Maximum 254 V AC Minimum 12 V AC Minimum 12 V DC
Rated Short-Circuit Capacity(AC) 15 kA (240 / 415 V AC) 15 kA (400 V) 25 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(240 V AC) 25 kA (72 V DC) 25 kA (230 V) 25 kA
Rated Service Short-Circuit Breaking Capacity (Ics)(240 V AC) 7.5 kA (72 V DC) 7.5 kA
Rated Insulation Voltage (Ui)acc. to IEC/EN 60664-1 500 V
Rated Impulse Withstand Voltage (Uimp)6 kV
Rated Frequency (f)50 / 60 Hz DC
StandardsCSA 22.2 No. 235 IEC/EN 60898-1 IEC/EN 60947-2 UL 1077
Electrical Endurance10000 AC cycle
Mechanical Endurance20000 cycle
Power Loss6 W at Rated Operating Conditions per Pole 6 W
Degree of ProtectionIP20 IP40 Enclosure with Cover IP40
Pollution Degree3
Ambient Air TemperatureOperation -40 ... +70 °C Storage -55 ... +70 °C
Terminal TypeScrew Terminals
Connecting CapacityBusbar 10/10 mm² Flexible with Ferrule 0.75 ... 25 mm² Flexible 0.75 ... 25 mm² Rigid 0.75 ... 35 mm² Stranded 0.75 ... 35 mm²
Tightening Torque2.8 N·m
Product Net Width17.5 mm
Product Net Height88 mm
Product Net Depth / Length67.6 mm
Product Net Weight0.128 kg

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.