AurFort
ABBS300PABB S302P-C4, manufacturer catalog image

ABB catalog image for this SKU; may represent the product family.

MINIATURE CIRCUIT BREAKER

S302P-C4

SKU 2CDS382001R0044

ABB S302P-C4 is a miniature circuit breaker, rated at 4 A with a 2P configuration. Tripping characteristic: C.

4 ARated current
2PPoles
CTrip curve
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 07, 2026.

2CDS382001R0044 — selected manufacturer specifications
Product ID2CDS382001R0044
Catalog DescriptionMiniature Circuit Breaker - S300P - 2P - 4 A - C - (415 V AC) 100 kA
Rated Current (In)4 A
Number of Poles2P
Number of Protected Poles2
Tripping CharacteristicC
Input Voltage TypeAC/DC
Rated Operational Voltageacc. to IEC 60898-1 415 V AC acc. to IEC 60947-2 415 V AC
Operational VoltageMaximum (Incl. Tolerance) 457 V AC Maximum 457 V AC Minimum 12 V AC Minimum 12 V DC
Rated Short-Circuit Capacity(415 V AC) 100 kA (440 V AC) 100 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(125 V DC) 100 kA (400 V AC) 100 kA (415 V AC) 100 kA (440 V AC) 100 kA (72 V DC) 25 kA
Rated Service Short-Circuit Breaking Capacity (Ics)(125 V DC) 100 kA (400 V AC) 100 kA (440 V AC) 100 kA
Rated Insulation Voltage (Ui)acc. to IEC/EN 60664-1 500 V
Rated Impulse Withstand Voltage (Uimp)6 kV
Rated Frequency (f)50 / 60 Hz DC
StandardsCSA 22.2 No. 235 IEC/EN 60898-1 IEC/EN 60947-2 UL 1077
Electrical Endurance20000 AC cycle
Mechanical Endurance20000 cycle
Power Loss2.8 W at Rated Operating Conditions per Pole 1.4 W
Degree of ProtectionIP20 IP40 Enclosure with Cover IP40
Pollution Degree3
Ambient Air TemperatureOperation -40 ... +70 °C Storage -55 ... +70 °C
Terminal TypeScrew Terminals
Connecting CapacityBusbar 10/10 mm² Flexible with Ferrule 0.75 ... 25 mm² Flexible 0.75 ... 25 mm² Rigid 0.75 ... 35 mm² Stranded 0.75 ... 35 mm²
Tightening Torque2.8 N·m
Product Net Width35 mm
Product Net Height88 mm
Product Net Depth / Length69 mm
Product Net Weight0.24 kg

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.