ABBC13

ABB catalog image for this SKU; may represent the product family.
ELECTRICITY METER
C13 110-101
SKU 2CMA103574R1000ABB C13 110-101: Electricity meter. Rated current: 5 A Maximum 40 A. Pole configuration: 4P.
5 A
Maximum 40 ARated current
4PPoles
C13Product range
PRODUCT DATA
Technical specifications
Source: ABB English regional product catalog.
Verified September 08, 2026.
| Product ID | 2CMA103574R1000 |
|---|---|
| Catalog Description | Energy meter 'Steel', 3-phase, 5 A |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 66.08 % |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill UL 2799 Zero Waste To Landfill Validation available |
| Improved Energy Efficiency for Customers | Process Efficiency - Product improves/optimizes process Process Efficiency - Product contribute to making customer’s operations more resilient and reliable Process Efficiency - Product contribute to reducing customer operations environmental footprint Digital Efficiency - Product is digitally-supported to optimize usage and eventually optimize customer asset |
| Extended Product Lifetime | Lifetime extension of customer’s assets is made possible thanks to offering and the supporting services |
| End Of Life Disassembling Instructions | 9AKK108470A1374 |
| Environmental Product Declaration - EPD | 9AKK108467A4138 |
| Function | Electricity meter |
| Sub-Function | Steel |
| Current Rating | 5 A |
| Communication Interface | None |
| Accuracy | Active Energy Class B MID (±1%) |
| Measuring Instrument Conformity | Measurement Instrument Directive (MID) |
| Meter Tariff Rating | One-Tariff |
| Pulse Output Rate | 1000 |
| Number of Poles | 4P |
| Number of Phases | 3-phase |
| Number of Counter Positions | 7 |
| Number of Digital In/Outputs | 1 Digital Output |
| Pulse Output Type | Electrical |
| Type of Indicator | Digital |
| Input Current Maximum (Iin) | 40 A |
| Rated Voltage (Ur) | 3x220-240 V |
| Voltage Range | 3x176…276 V |
| Rated Current (In) | 5 A Maximum 40 A |
| Rated Frequency (f) | 50 / 60 Hz |
| Power Consumption (@Pcons) | 0.72 W |
| Power Loss | 0.64 W |
| Enclosure Material | Polycarbonate in transparent front glass and terminal cover. Glass reinforced polycarbonate in housing. |
| RoHS Declaration | 2CMC486006 |
| RoHS Information | Following EU Directive 2002/95/EC August 18, 2005 and amendment |
| RoHS Date | 20190722 |
| REACH Declaration | 9AKK108467A9482 |
| REACH Information | True - contains substances > 0.1 mass percentage |
| REACH Date | 20240429 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108468A3363 |
| Ambient Air Temperature | Operation -25 ... 70 °C |
| Degree of Protection | IP20 |
| Width in Number of Modular Spacings | 3 |
| Product Net Width | 54 mm |
| Product Net Height | 26.5 mm |
| Product Net Depth / Length | 65 mm |
| Product Net Weight | 170 g |
| Dimension Diagram | 2CMC486004M0201 |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 88 mm |
| Package Level 1 Height | 68 mm |
| Package Level 1 Depth / Length | 116 mm |
| Package Level 1 Gross Weight | 2288 g |
| Package Level 1 EAN | 7392696035743 |
| Package Level 2 Units | box 24 piece |
| Package Level 2 Width | 240 mm |
| Package Level 2 Height | 174 mm |
| Package Level 2 Depth / Length | 426 mm |
| Package Level 2 Gross Weight | 6.100 kg |
| Package Level 2 EAN | 7392696059435 |
| Minimum Order Quantity | 1 piece |
| E-Number (Finland) | 6701065 |
| Replacement Product ID (NEW) | 2CMA241695R1000 |
| Declaration of Conformity - CE | 2CMC486004D0001 |
| EU Data Act Compliance Declaration | Not applicable |
| Instructions and Manuals | 2CMC486006M0201 |
| Data Sheet, Technical Information | 2CMC486004M0201 |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.