AurFort
ABBA43ABB A43 512-100, manufacturer catalog image

ABB catalog image for this SKU; may represent the product family.

ELECTRICITY METER

A43 512-100

SKU 2CMA170531R1000

ABB A43 512-100: Electricity meter. Rated current: Maximum 80 A. Pole configuration: 4P.

Maximum 80 ARated current
4PPoles
A43Product range
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 08, 2026.

2CMA170531R1000 — selected manufacturer specifications
Product ID2CMA170531R1000
ABB Type DesignationA43 512-100
Catalog DescriptionEnergy meter 'Platinum', Modbus RTU, 3-phase, 5 A
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 66.08 %
ABB Site Meeting Group Waste To Landfill TargetNo non-hazardous waste is sent to a landfill UL 2799 Zero Waste To Landfill Validation available
Improved Energy Efficiency for CustomersProcess Efficiency - Product improves/optimizes process Process Efficiency - Product contribute to making customer’s operations more resilient and reliable Process Efficiency - Product contribute to reducing customer operations environmental footprint Digital Efficiency - Product is digitally-supported to optimize usage and eventually optimize customer asset
Extended Product LifetimeLifetime extension of customer’s assets is made possible thanks to offering and the supporting services
End Of Life Disassembling Instructions9AKK108470A1374
Environmental Product Declaration - EPD9AKK108467A4138
FunctionElectricity meter
Sub-FunctionPlatinum
Current Rating5 A
Communication InterfaceRS-485
AccuracyActive Energy Class B MID (±1%)
Measuring Instrument ConformityMeasurement Instrument Directive (MID)
Meter Tariff ControlInternal External
Meter Tariff RatingMulti-Tariff
Pulse Output Rate1 … 9999 kvar·h
Model NumberDirect measurement
Number of Poles4P
Number of Phases3-phase
Number of Counter Positions7
Number of Digital In/Outputs4 I/O Channels
Real-time ClockReal time clock with 5 ppm accuracy at reference temperature 25°C
Energy Meter TypeAC-MID
Pulse Output TypeElectrical
Type of IndicatorDigital
CommunicationModbus RTU
Connecting Capacity Main Circuit1 ... 25 mm²
Input Current Maximum (Iin)80 A
Rated Voltage (Ur)57.7…400 (Un) N-L V 100…500 (Un) L-L V
Voltage Range3x47…331 V
Rated Current (In)Maximum 80 A
Frequency (f)50 … 60 Hz
Rated Frequency (f)50 / 60 Hz
Power Consumption (@Pcons)0.807 W
Enclosure MaterialPolycarbonate in transparent front glass. Glass reinforced polycarbonate in bottom case and upper case. Polycarbonate in terminal cover.
RoHS Declaration9AKK108470A3626
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
RoHS Date20260203
REACH Declaration9AKK108467A9482
REACH InformationTrue - contains substances > 0.1 mass percentage
REACH Date20240429
Conflict Minerals Reporting Template (CMRT)9AKK108468A3363
Ambient Air TemperatureOperation -40 ... 70 °C
Degree of ProtectionIP20
Environmental Information2CMC484004D0001
Width in Number of Modular Spacings7
Product Net Width123 mm
Product Net Height26.5 mm
Product Net Depth / Length65 mm
Product Net Weight448 g
Size97X123X65
Package Level 1 Unitsbox 1 piece
Package Level 1 Width98 mm
Package Level 1 Height68 mm
Package Level 1 Depth / Length144 mm
Package Level 1 Gross Weight0.538 kg
Package Level 1 EAN7392696705318
Minimum Order Quantity1 piece
E-Number (Finland)6625011
E-Number (Norway)8204035
E-Number (Sweden)0980713
Declaration of Conformity - CE9AKK108470A3626
EU Data Act Compliance Declaration9AKK108471A5047
Instructions and Manuals2CMC484003M0201
Data Sheet, Technical Information2CMC484001M0201
IDEA Granular Category Code (IGCC)3300 >> Kilowatt-hour meter
StandardsEN 50470-1

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.