AurFort
VigiPacTSchneider Electric rectangular sensor L1 type, Vigirex, 280 mm X 115 mm, 1600 A, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

EARTH LEAKAGE CURRENT SENSOR

rectangular sensor L1 type, Vigirex, 280 mm X 115 mm, 1600 A

SKU 56053

Schneider Electric 56053 is a earth leakage current sensor in the VigiPacT range. Key specifications include mounting mode: Fixed (cables); ip protection: Body: IP30; net weight: 11 kg.

Fixed (cables)Mounting mode
Body: IP30IP protection
11 kgNet weight
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 17, 2026.

56053 — selected manufacturer specifications
Product reference56053
RangeVigiPacT
Device short nameL
Product or component typeEarth leakage current sensor
Device applicationEquipment monitoring and control
Range compatibilityVigiPacT RH10M residual current protection relay VigiPacT RH10P residual current protection relay VigiPacT RH21M residual current protection relay VigiPacT RH21P residual current protection relay VigiPacT RH68M residual current protection relay VigiPacT RH86M residual current protection relay VigiPacT RH86P residual current protection relay VigiPacT RH99M residual current protection relay VigiPacT RH99P residual current protection relay VigiPacT RH197M residual current protection relay VigiPacT RH197P residual current protection relay VigiPacT RHU residual current protection relay VigiPacT RHUs residual current protection relay VigiPacT RMH residual current protection relay
current sensor typeRectangular sensor
[Ie] rated operational current1600 A
Transformer ratio1/1000
Network frequency50/60 Hz 400 Hz
[Icw] rated short-time withstand current100 kA for 0.5 s
Residual short-circuit withstand current85 kA / 0.5 s
[Ui] rated insulation voltage1000 V
Overvoltage categoryIV
[Uimp] rated impulse withstand voltage12 kV
Mounting modeFixed (cables) Fixed (busbar)
Connections - terminalsScrew connection 0.5…2.5 mm²
Net weight11 kg
HeightOutside: 233 mm Inside: 115 mm
WidthOutside: 388 mm Inside: 280 mm
Depth72 mm
IP degree of protectionBody: IP30 Connectors: IP20
Environmental characteristicExposure to damp heat in service: category C2: 48 hours conforming to IEC 60068-2-56 Exposure to damp heat not in service (25...55 °C, RH 95 %) : 28 cycles conforming to IEC 60068-2-30 Salt mist: Kb/2 conforming to IEC 60068-2-52
Pollution degreeLevel 3 conforming to IEC 60664-1
Ambient air temperature for operation-35…80 °C
Ambient air temperature for storage-55…100 °C
StandardsIEC 60947-2
Product certificationsCE