AurFort
VigiPacTSchneider Electric rectangular sensor L2 type, Vigirex, 470 mm X 160 mm, 1600 A, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

EARTH LEAKAGE CURRENT SENSOR

rectangular sensor L2 type, Vigirex, 470 mm X 160 mm, 1600 A

SKU 56054

Schneider Electric 56054 is a earth leakage current sensor in the VigiPacT range. Key specifications include mounting mode: Fixed (cables); ip protection: Body: IP30; net weight: 20 kg.

Fixed (cables)Mounting mode
Body: IP30IP protection
20 kgNet weight
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 06, 2026.

56054 — selected manufacturer specifications
Product reference56054
RangeVigiPacT
Device short nameL
Product or component typeEarth leakage current sensor
Device applicationEquipment monitoring and control
Range compatibilityVigiPacT RH10M residual current protection relay VigiPacT RH10P residual current protection relay VigiPacT RH21M residual current protection relay VigiPacT RH21P residual current protection relay VigiPacT RH68M residual current protection relay VigiPacT RH86M residual current protection relay VigiPacT RH86P residual current protection relay VigiPacT RH99M residual current protection relay VigiPacT RH99P residual current protection relay VigiPacT RH197M residual current protection relay VigiPacT RH197P residual current protection relay VigiPacT RHU residual current protection relay VigiPacT RHUs residual current protection relay VigiPacT RMH residual current protection relay
current sensor typeRectangular sensor
[Ie] rated operational current3200 A
Transformer ratio1/1000
Network frequency50/60 Hz 400 Hz
[Icw] rated short-time withstand current100 kA for 0.5 s
Residual short-circuit withstand current85 kA / 0.5 s
[Ui] rated insulation voltage1000 V
Overvoltage categoryIV
[Uimp] rated impulse withstand voltage12 kV
Mounting modeFixed (cables) Fixed (busbar)
Connections - terminalsScrew connection 0.5…2.5 mm²
Net weight20 kg
HeightOutside: 266 mm Inside: 160 mm
WidthOutside: 576 mm Inside: 470 mm
Depth72 mm
IP degree of protectionBody: IP30 Connectors: IP20
Environmental characteristicExposure to damp heat in service: category C2: 48 hours conforming to IEC 60068-2-56 Exposure to damp heat not in service (25...55 °C, RH 95 %) : 28 cycles conforming to IEC 60068-2-30 Salt mist: Kb/2 conforming to IEC 60068-2-52
Pollution degreeLevel 3 conforming to IEC 60664-1
Ambient air temperature for operation-35…80 °C
Ambient air temperature for storage-55…100 °C
StandardsIEC 60947-2
Product certificationsCE

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.