Schneider Electric catalog image for this SKU; may represent the product family.
EARTH LEAKAGE CURRENT SENSOR
rectangular sensor L2 type, Vigirex, 470 mm X 160 mm, 1600 A
SKU 56054Schneider Electric 56054 is a earth leakage current sensor in the VigiPacT range. Key specifications include mounting mode: Fixed (cables); ip protection: Body: IP30; net weight: 20 kg.
Fixed (cables)Mounting mode
Body: IP30IP protection
20 kgNet weight
PRODUCT DATA
Technical specifications
Source: Schneider Electric product catalog.
Verified September 06, 2026.
| Product reference | 56054 |
|---|---|
| Range | VigiPacT |
| Device short name | L |
| Product or component type | Earth leakage current sensor |
| Device application | Equipment monitoring and control |
| Range compatibility | VigiPacT RH10M residual current protection relay VigiPacT RH10P residual current protection relay VigiPacT RH21M residual current protection relay VigiPacT RH21P residual current protection relay VigiPacT RH68M residual current protection relay VigiPacT RH86M residual current protection relay VigiPacT RH86P residual current protection relay VigiPacT RH99M residual current protection relay VigiPacT RH99P residual current protection relay VigiPacT RH197M residual current protection relay VigiPacT RH197P residual current protection relay VigiPacT RHU residual current protection relay VigiPacT RHUs residual current protection relay VigiPacT RMH residual current protection relay |
| current sensor type | Rectangular sensor |
| [Ie] rated operational current | 3200 A |
| Transformer ratio | 1/1000 |
| Network frequency | 50/60 Hz 400 Hz |
| [Icw] rated short-time withstand current | 100 kA for 0.5 s |
| Residual short-circuit withstand current | 85 kA / 0.5 s |
| [Ui] rated insulation voltage | 1000 V |
| Overvoltage category | IV |
| [Uimp] rated impulse withstand voltage | 12 kV |
| Mounting mode | Fixed (cables) Fixed (busbar) |
| Connections - terminals | Screw connection 0.5…2.5 mm² |
| Net weight | 20 kg |
| Height | Outside: 266 mm Inside: 160 mm |
| Width | Outside: 576 mm Inside: 470 mm |
| Depth | 72 mm |
| IP degree of protection | Body: IP30 Connectors: IP20 |
| Environmental characteristic | Exposure to damp heat in service: category C2: 48 hours conforming to IEC 60068-2-56 Exposure to damp heat not in service (25...55 °C, RH 95 %) : 28 cycles conforming to IEC 60068-2-30 Salt mist: Kb/2 conforming to IEC 60068-2-52 |
| Pollution degree | Level 3 conforming to IEC 60664-1 |
| Ambient air temperature for operation | -35…80 °C |
| Ambient air temperature for storage | -55…100 °C |
| Standards | IEC 60947-2 |
| Product certifications | CE |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.