AurFort
Acti9 iC60Schneider Electric Miniature circuit breaker (MCB), Acti9 iC60H, 1P, 63A, C curve, 10000A (IEC/EN 60898-1), 15kA (IEC/EN 60947-2), manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

MINIATURE CIRCUIT-BREAKER

Miniature circuit breaker (MCB), Acti9 iC60H, 1P, 63A, C curve, 10000A (IEC/EN 60898-1), 15kA (IEC/EN 60947-2)

SKU A9F84163

Schneider Electric A9F84163 is a miniature circuit-breaker in the Acti9 iC60 range. Key specifications include rated current: 63 A; poles: 1P; trip curve: C.

63 ARated current
1PPoles
CTrip curve
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 17, 2026.

A9F84163 — selected manufacturer specifications
Product referenceA9F84163
RangeActi9
Product nameActi9 iC60
Product or component typeMiniature circuit-breaker
Device short nameiC60H
Device applicationDistribution
Poles description1P
Number of protected poles1
[In] rated current63 A
Network typeDC AC
Trip unit technologyThermal-magnetic
Curve codeC
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Suitability for isolationYes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1
StandardsEN/IEC 60947-2 EN/IEC 60898-1
Network frequency50/60 Hz
[Ue] rated operational voltage12...60 V AC 50/60 Hz 100...133 V AC 50/60 Hz 220...240 V AC 50/60 Hz 12...60 V DC 60...72 V DC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 15 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
[Ics] rated service breaking capacity21 kA 50 % x Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA 50 % x Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 7.5 kA 50 % x Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA 100 % x Icu at 12...60 V DC conforming to EN/IEC 60947-2 15 kA 100 % x Icu at 60...72 V DC conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2
Contact position indicatorYes
Control typeToggle
Local signallingTrip indicator
Mounting modeClip-on Removable comb busbar installed
Mounting support35 mm DIN rail
Comb busbar and distribution block compatibilityTop or bottom: YES
Connection pitch18 mm between devices
9 mm pitches2
Height85 mm
Width18 mm
Depth78.5 mm
Net weight0.215 kg
ColourWhite
Mechanical durability20000 cycles
Electrical durability10000 cycles
Connections - terminalsSingle terminal (top or bottom) , for 1 cable(s) , 1…35 mm², rigid, copper Single terminal (top or bottom) , for 3.0 cable(s) , 16 mm², rigid, copper, with accessory Single terminal (top or bottom) , for 1.0 cable(s) , 50 mm², rigid, aluminium, with accessory Single terminal (top or bottom) , for 1.0 cable(s) , 1…25 mm², flexible, copper Single terminal (top or bottom) , for 1.0 cable(s) , 1…25 mm², flexible with ferrule, copper Single terminal (top or bottom) , for 1.0 cable(s) , flexible, copper or aluminium, with ring terminal and accessory Single terminal (top or bottom) , for 3 cable(s) , 10 mm², flexible, copper, with accessory
Wire stripping length14 mm for top or bottom connection
Tightening torque3.5 N.m top or bottom
Earth-leakage protectionWithout
IP degree of protectionIP20 conforming to IEC 60529 IP40 in modular enclosure (Insulation class II) conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Overvoltage categoryIV
Tropicalisation2 conforming to IEC 60068-1
Relative humidity95 % at 55 °C
Operating altitude0...2000 m
Ambient air temperature for operation-35…70 °C
Ambient air temperature for storage-40…85 °C

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.