Schneider Electric catalog image for this SKU; may represent the product family.
ADD-ON RESIDUAL CURRENT DEVICE
Vigi C120 - earth leakage add-on block - 2P - 300 mA - class AC
SKU A9N18564Schneider Electric A9N18564 is a add-on residual current device in the Acti9 Vigi C120 range. Key specifications include mounting mode: Clip-on; rated current: 125 A; poles: 2P.
Clip-onMounting mode
125 ARated current
2PPoles
PRODUCT DATA
Technical specifications
Source: Schneider Electric product catalog.
Verified September 18, 2026.
| Product reference | A9N18564 |
|---|---|
| Range | Acti9 |
| Product name | Acti9 Vigi C120 |
| Product or component type | Add-on residual current device |
| Device short name | Vigi C120 |
| Poles description | 2P |
| [In] rated current | 125 A |
| Network type | AC |
| Earth-leakage sensitivity | 300 mA |
| Earth-leakage protection time delay | Instantaneous |
| Earth-leakage protection class | Type AC |
| Standards | EN 61009 IEC/EN 61009-2-1 |
| Device location in system | Outgoer Group incomer |
| Network frequency | 50/60 Hz |
| [Ue] rated operational voltage | 230...415 V AC 50/60 Hz |
| Residual current tripping technology | Voltage independent |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to IEC 60947-1 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Mounting mode | Clip-on |
| Mounting support | 35 mm symmetrical DIN rail |
| Electrical connection to mcb | By screws |
| 9 mm pitches | 7 |
| Height | 95 mm |
| Width | 117 mm |
| Depth | 73 mm |
| Net weight | 0.325 kg |
| Colour | White |
| Mechanical durability | 20000 cycles |
| Connections - terminals | Tunnel type terminals 1…35 mm² flexible Tunnel type terminals 1…50 mm² rigid |
| Wire stripping length | 15 mm |
| Tightening torque | 3.5 N.m |
| IP degree of protection | IP20 |
| Pollution degree | 3 conforming to IEC 60947-2 |
| Ambient air temperature for operation | -5…60 °C |
| Ambient air temperature for storage | -40…60 °C |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.