AurFort
Acti9 iID KSchneider Electric Acti 9 iID K - residual current circuit breaker - 2P - 25A - 300mA - type AC, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

RESIDUAL CURRENT CIRCUIT BREAKER (RCCB)

Acti 9 iID K - residual current circuit breaker - 2P - 25A - 300mA - type AC

SKU A9R75225

Schneider Electric A9R75225 is a residual current circuit breaker (rccb) in the Acti9 iID K range. Key specifications include rated current: 25 A; poles: 2P; residual sensitivity: 300 mA.

25 ARated current
2PPoles
300 mAResidual sensitivity
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 18, 2026.

A9R75225 — selected manufacturer specifications
Product referenceA9R75225
RangeActi9
Product nameActi9 iID K
Product or component typeResidual current circuit breaker (RCCB)
Device short nameiID K
Poles description2P
Neutral positionLeft
[In] rated current25 A
Network typeAC
Earth-leakage sensitivity300 mA
Earth-leakage protection time delayInstantaneous
Earth-leakage protection classType AC
Quality labelsVDE
Device location in systemOutgoer
Network frequency50/60 Hz
[Ue] rated operational voltage220...240 V AC 50/60 Hz
Residual current tripping technologyVoltage independent
Rated breaking and making capacityIdm 500 A Im 500 A
Rated conditional short-circuit currentGL63: Inc 4.5 kA K60: Inc 6 kA C60: Inc 6 kA
[Ui] rated insulation voltage440 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage4 kV
Surge current250 A
Contact position indicatorNo
Control typeToggle
Mounting modeClip-on
Mounting support35 mm DIN rail
9 mm pitches4
Height85 mm
Width36 mm
Depth69 mm
Net weight0.21 kg
ColourWhite
Mechanical durability5000 cycles
Electrical durabilityAC-1: 2000 cycles
Locking options descriptionPadlocking device
Connections - terminalsTunnel type terminals top or bottom 1…35 mm² rigid Tunnel type terminals top or bottom 1…25 mm² flexible Tunnel type terminals top or bottom 1…25 mm² flexible with ferrule
Wire stripping length16 mm for top or bottom connection
Tightening torque3.5 N.m top or bottom
StandardsEN/IEC 61008-1 EN/IEC 61008-2-1
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree2
Electromagnetic compatibility8/20 µs impulse withstand, 200 A conforming to EN/IEC 61008-1
Ambient air temperature for operation-5…60 °C
Ambient air temperature for storage-40…85 °C

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.