AurFort
Altivar Machine ATV340Schneider Electric variable speed drive, Altivar Machine ATV340, 37kW, heavy duty, 400V, 3 phases, Ethernet, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

VARIABLE SPEED DRIVE

variable speed drive, Altivar Machine ATV340, 37kW, heavy duty, 400V, 3 phases, Ethernet

SKU ATV340D37N4E

Schneider Electric ATV340D37N4E is a variable speed drive in the Altivar Machine ATV340 range. Key specifications include motor power: 45 kW for normal duty; supply voltage: 380...480 V - 15...10 %; supply phases: 3 phases.

45 kW for normal dutyMotor power
380...480 V - 15...10 %Supply voltage
3 phasesSupply phases
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 06, 2026.

ATV340D37N4E — selected manufacturer specifications
Product referenceATV340D37N4E
Range of productAltivar Machine ATV340
Product or component typeVariable speed drive
Product specific applicationMachine
Mounting modeWall mount
VariantStandard version
Communication port protocolModbus TCP Modbus serial EtherNet/IP
Option cardCommunication module, PROFINET Communication module, DeviceNet Communication module, CANopen Communication module, EtherCAT
Network number of phases3 phases
Supply frequency50...60 Hz +/- 5 %
[Us] rated supply voltage380...480 V - 15...10 %
nominal output current74.5 A
Motor power kW45 kW for normal duty 37 kW for heavy duty
Motor power hp60 hp for normal duty 50 hp for heavy duty
EMC filterClass C3 EMC filter integrated
IP degree of protectionIP20
Degree of protectionUL type 1
Discrete input number8
Discrete input typePTI safe torque off: 0…30 kHz, 24 V DC (30 V) DI1...DI5 programmable as pulse input, 24 V DC (30 V), impedance: 3.5 kOhm programmable
number of preset speeds16 preset speeds
Discrete output number1.0
Discrete output typeProgrammable output DQ1, DQ2 30 V DC 100 mA
Analogue input number3
Analogue input typeAI1 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits AI1 software-configurable temperature probe or water level sensor AI1 software-configurable voltage: 0...10 V DC, impedance: 31.5 kOhm, resolution 12 bits AI2 software-configurable voltage: - 10...10 V DC, impedance: 31.5 kOhm, resolution 12 bits
Analogue output number2
Analogue output typeSoftware-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits Software-configurable current AQ1, AQ2: 0...20 mA impedance 500 Ohm, resolution 10 bits
Relay output number3
Output voltage<= power supply voltage
Relay output typeRelay outputs R1A Relay outputs R1C electrical durability 100000 cycles Relay outputs R2A Relay outputs R2C electrical durability 100000 cycles
Maximum switching currentRelay output R1C on resistive load, cos phi = 1: 3 A at 250 V AC Relay output R1C on resistive load, cos phi = 1: 3 A at 30 V DC Relay output R1C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R1C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC Relay output R2C on resistive load, cos phi = 1: 5 A at 250 V AC Relay output R2C on resistive load, cos phi = 1: 5 A at 30 V DC Relay output R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
Minimum switching currentRelay output R1B: 5 mA at 24 V DC Relay output R2C: 5 mA at 24 V DC
Physical interface2-wire RS 485
Connector type3 RJ45
Method of accessSlave Modbus RTU Slave Modbus TCP
Transmission rate4.8 kbit/s 9.6 kbit/s 19.2 kbit/s 38.4 kbit/s
Transmission frameRTU
Number of addresses1…247
Data format8 bits, configurable odd, even or no parity
Type of polarizationNo impedance
4 quadrant operation possibleTrue
Asynchronous motor control profileOptimized torque mode Variable torque standard Constant torque standard
Synchronous motor control profileReluctance motor Permanent magnet motor
Pollution degree2
Maximum output frequency0.599 kHz
Acceleration and deceleration rampsLinear adjustable separately from 0.01...9999 s S, U or customized
Motor slip compensationAdjustable Can be suppressed Automatic whatever the load Not available in permanent magnet motor law
Switching frequency2...16 kHz adjustable 4...16 kHz with derating factor
Nominal switching frequency4 kHz
Braking to standstillBy DC injection
Brake chopper integratedTrue
Line current79.8 A at 380 V with internal line choke (normal duty) 69.1 A at 480 V with internal line choke (normal duty) 67.1 A at 380 V with internal line choke (heavy duty) 59 A at 480 V with internal line choke (heavy duty) 67.1 A 59.0 A
Maximum input current79.8 A
Maximum output voltage480 V
Apparent power57.4 kVA at 480 V (normal duty) 49.1 kVA at 480 V (heavy duty)
Maximum transient current105.6 A during 60 s (normal duty) 105.6 A during 2 s (normal duty) 111.8 A during 60 s (heavy duty) 111.8 A during 2 s (heavy duty)
Electrical connectionControl: screw terminal 0.75...1.5 mm²/18 AWG...16 AWG Line side: screw terminal 35...50 mm²/2 AWG...1 AWG DC bus: screw terminal 35...50 mm²/3 AWG...1 AWG Motor: screw terminal 50 mm²/1 AWG
Prospective line Isc50 kA
Base load current at high overload74.5 A
Base load current at low overload88.0 A
Power dissipation in WNatural convection: 90 W at 380 V, switching frequency 4 kHz (heavy duty) Forced convection: 796 W at 380 V, switching frequency 4 kHz (heavy duty) Natural convection: 105 W at 380 V, switching frequency 4 kHz (normal duty) Forced convection: 943 W at 380 V, switching frequency 4 kHz (normal duty)
With safety function Safely Limited Speed (SLS)True
With safety function Safe brake management (SBC/SBT)True
With safety function Safe Operating Stop (SOS)False
With safety function Safe Position (SP)False
With safety function Safe programmable logicFalse
With safety function Safe Speed Monitor (SSM)False
With safety function Safe Stop 1 (SS1)True
With sft fct Safe Stop 2 (SS2)False
With safety function Safe torque off (STO)True
With safety function Safely Limited Position (SLP)False
With safety function Safe Direction (SDI)False
Protection typeThermal protection: motor Safe torque off: motor Motor phase loss: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent: drive Output overcurrent between motor phase and earth: drive Output overcurrent between motor phases: drive Short-circuit between motor phase and earth: drive Short-circuit between motor phases: drive Motor phase loss: drive DC Bus overvoltage: drive Line supply overvoltage: drive Line supply undervoltage: drive Input supply loss: drive Exceeding limit speed: drive Break on the control circuit: drive
Width213.0 mm
Height660.0 mm
Depth262.0 mm
Net weight28.4 kg
Continuous output current88 A at 4 kHz for normal duty 74.5 A at 4 kHz for heavy duty
Operating altitude<= 4800 m with current derating above 1000m
Operating positionVertical +/- 10 degree
Product certificationsUL CSA TÜV EAC CTick
MarkingCE
StandardsIEC 61800-3 IEC 61800-5-1 IEC 60721-3 IEC 61508 IEC 13849-1 UL 618000-5-1 UL 508C IEC 61000-3-12
Maximum THDI<48 % full load conforming to IEC 61000-3-12 <48 % 80 % load conforming to IEC 61000-3-12
Assembly styleWith heat sink
Electromagnetic compatibilityElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Environmental class (during operation)Class 3C3 according to IEC 60721-3-3 Class 3S3 according to IEC 60721-3-3
Maximum acceleration under shock impact (during operation)150 m/s² at 11 ms
Maximum acceleration under vibrational stress (during operation)10 m/s² at 13...200 Hz
Maximum deflection under vibratory load (during operation)1.5 mm at 2...13 Hz
Permitted relative humidity (during operation)Class 3K5 according to EN 60721-3
Volume of cooling air240.0 m3/h
Type of coolingForced convection
Overvoltage categoryClass III
Regulation loopAdjustable PID regulator
Noise level63.5 dB
Ambient air transport temperature-40…70 °C
Ambient air temperature for operation-15…50 °C without derating (vertical position) 50…60 °C with derating factor (vertical position)
Ambient air temperature for storage-40…70 °C
IsolationBetween power and control terminals

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.