AurFort
ComPacT NS new generationSchneider Electric Circuit breaker, ComPacT NS800H, 70kA at 415VAC, 3P, fixed, manually operated, MicroLogic 5.0E control unit, 800A, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

CIRCUIT BREAKER

Circuit breaker, ComPacT NS800H, 70kA at 415VAC, 3P, fixed, manually operated, MicroLogic 5.0E control unit, 800A

SKU C080H35EFM

Schneider Electric C080H35EFM is a circuit breaker in the ComPacT NS new generation range. Key specifications include rated current: 800 A at 50 °C; poles: 3P; trip unit: MicroLogic 5.0 E.

800 A at 50 °CRated current
3PPoles
MicroLogic 5.0 ETrip unit
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 18, 2026.

C080H35EFM — selected manufacturer specifications
Product referenceC080H35EFM
RangeComPacT
Product nameComPacT NS new generation
Range of productComPacT NS630b...1600 new generation
Product or component typeCircuit breaker
Device applicationDistribution
Number of poles3P
Protected poles description3D
[In] rated current800 A at 50 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory B
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH 70 kA 415 V AC
Trip unit nameMicroLogic 5.0 E
Trip unit technologyElectronic
Trip unit protection functionsLSI
Control typeManually operated
Mounting modeFixed
[Ui] rated insulation voltage800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2
[Ics] rated service breaking capacity50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Icw] rated short-time withstand current19.2 kA 1 s conforming to IEC 60947-2
Mechanical durability10000 cycles
Electrical durability2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Power losses15 W
Mounting supportBackplate
Upside connectionFront
Downside connectionFront
Connection pitch70 mm
Protection typeL : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection
Trip unit rating800 A at 50 °C
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Long-time protection delay adjustment type trAdjustable 9 settings
[tr] long-time delay adjustment range12.5…600 s at 1.5 x Ir 0.5…24 s at 6 x Ir 0.7…16.6 s at 7.2 x Ir
Thermal memory20 mn
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdAdjustable
[tsd] short-time delay adjustment range0.1…0.4 s I²t=on 0…0.4 s I²t=off
Instantaneous protection pick-up adjustment type IiAdjustable
[Ii] instantaneous protection pick-up adjustment rangeOff 2...15 x In
Earth-leakage protectionWithout
Zone selective interlocking ZSIWith
Auxiliary contact composition1 NO/NC
Local signalling4 LEDs (red) for fault indication 1 LED (yellow) for overload
Display typeLCD display
Type of measurementEnergy meter
Width (W)210 mm
Height (H)327 mm
Depth (D)147 mm
Net weight14 kg
StandardsEN/IEC 60947-2
Product certificationsIECEE CB Scheme
Overvoltage categoryIII
Electrical shock protection classClass II on front face
Pollution degree3 conforming to IEC 60947
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-40…85 °C
Relative humidity0…95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating