AurFort
ComPacT NSXSchneider Electric Circuit breaker, ComPacT NSX100F, 36kA/415VAC, 4 poles 3D (neutral not protected), TMD trip unit 25A, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

CIRCUIT BREAKER

Circuit breaker, ComPacT NSX100F, 36kA/415VAC, 4 poles 3D (neutral not protected), TMD trip unit 25A

SKU C10F6TM025

Schneider Electric C10F6TM025 is a circuit breaker in the ComPacT NSX range. Key specifications include rated current: 25 A at 40 °C; poles: 4P; trip unit: TM-D.

25 A at 40 °CRated current
4PPoles
TM-DTrip unit
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 18, 2026.

C10F6TM025 — selected manufacturer specifications
Product referenceC10F6TM025
RangeComPacT
Product nameComPacT NSX
Device short nameNSX100F
Product or component typeCircuit breaker
Device applicationDistribution
Poles description4P
Protected poles description3D
Neutral positionLeft
[In] rated current25 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Breaking capacity codeF 36 kA 415 V AC
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Trip unit protection functionsLI
Control typeToggle
Circuit breaker mounting modeFixed
[Ui] rated insulation voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service breaking capacity85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability50000 cycles
Electrical durability50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Power dissipation per pole4.01 W
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Upside connectionFront
Downside connectionFront
Connection pitch35 mm
Protection typeL : for overload protection (thermal) I : for short-circuit protection (magnetic)
Trip unit rating25 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)Adjustable
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Long-time protection delay adjustment type trFixed
[tr] long-time delay adjustment range120…400 s at 1.5 x In 15 s at 6 x Ir
Neutral protection settingNo protection (3D)
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range300 A
Earth-leakage protectionWithout
Number of slots5 slot(s)
Width (W)140 mm
Height (H)161 mm
Depth (D)86 mm
Net weight2.4 kg
StandardsEN/IEC 60947-2
Overvoltage categoryIII
Electrical shock protection classClass II on front face
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Relative humidity0…95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.