AurFort
ComPacT NSXSchneider Electric Circuit breaker basic frame, ComPacT NSX100N, 50kA at 415VAC 50/60 Hz, 100A, without trip unit, 3 poles, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

BASIC FRAME

Circuit breaker basic frame, ComPacT NSX100N, 50kA at 415VAC 50/60 Hz, 100A, without trip unit, 3 poles

SKU C10N3

Schneider Electric C10N3 is a basic frame in the ComPacT NSX range. Key specifications include mounting mode: Fixed; rated current: 100 A at 40 °C; poles: 3P.

FixedMounting mode
100 A at 40 °CRated current
3PPoles
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 18, 2026.

C10N3 — selected manufacturer specifications
Product referenceC10N3
RangeComPacT
Product nameComPacT NSX
Device short nameNSX100N
Product or component typeBasic frame
Device applicationDistribution
Poles description3P
[In] rated current100 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Breaking capacity10 kA at 600 V AC 50/60 Hz conforming to UL 508 85 kA at 240 V AC 50/60 Hz conforming to UL 508 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 480 V AC 50/60 Hz conforming to UL 508 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN 50 kA 415 V AC
Control typeToggle
Mounting modeFixed
[Ui] rated insulation voltage800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2
[Ics] rated service breaking capacity10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability50000 cycles conforming to IEC 60947-2
Electrical durability10000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 20000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 30000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 50000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mounting supportBackplate
Upside connectionFront
Downside connectionFront
Connection pitch35 mm
Protection typeWithout protection
Width (W)105 mm
Height (H)161 mm
Depth (D)86 mm
StandardsEN/IEC 60947-2 UL 60947-4-1
Overvoltage categoryIII
Electrical shock protection classClass II on front face
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C