AurFort
ComPacT NSX100...250Schneider Electric Trip unit MicroLogic 5.2 E for ComPacT NSX 160/250 circuit breakers, electronic, rating 160A, 4 poles 4d, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

TRIP UNIT

Trip unit MicroLogic 5.2 E for ComPacT NSX 160/250 circuit breakers, electronic, rating 160A, 4 poles 4d

SKU C1645E160

Schneider Electric C1645E160 is a trip unit in the ComPacT NSX100...250 range. Key specifications include poles: 4P; trip unit: MicroLogic 5.2 E; operational voltage: 690 V AC 50/60 Hz.

4PPoles
MicroLogic 5.2 ETrip unit
690 V AC 50/60 HzOperational voltage
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 18, 2026.

C1645E160 — selected manufacturer specifications
Product referenceC1645E160
RangeComPacT
Range of productComPacT NSX100...250
Product or component typeTrip unit
Trip unit nameMicroLogic 5.2 E
Trip unit technologyElectronic
Range compatibilityComPacT NSX160 ComPacT NSX250
Device applicationDistribution
Poles description4P
Protected poles description3D + N/2 4D 3D + OSN 3D
Neutral positionLeft
Trip unit protection functionsLSI
Protection typeL : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection
Trip unit rating160 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Circuit breaker mounting modeFixed
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range63...160 A
Long-time protection delay adjustment type trAdjustable
[tr] long-time protection delay adjustment range15…400 s at 1.5 x Ir 0.35…11 s at 7.2 x Ir 0.5…16 s at 6 x Ir
Neutral protection settings0.5 x Ir (3D + N/2) 1 x Ir (4D) 1.6 x Ir (3D + OSN) No protection (3D)
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdAdjustable
[tsd] Short-time protection delay adjustment range0…0.4 s I²t=off 0.1…0.4 s I²t=on
Instantaneous protection pick-up adjustment type IiAdjustable
[Ii] instantaneous protection pick-up adjustment range1.5...15 x In
Earth-leakage protectionWithout
Zone selective interlocking ZSIWith
Local signallingFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Display typeLCD display
Type of measurementEnergy meter
Communication of dataEnergy metering Protection and alarm settings Time-stamped histories and event tables Instantaneous and demand values Maintenance indicators Demand current and power Power quality Maximeters/minimeters
Electrical data recordingMaintenance indicators
StandardsEN/IEC 60947-2
Electrical shock protection classClass II
Pollution degree3 conforming to IEC 60947-1
IP degree of protectionIP40 conforming to IEC 60529
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-40…85 °C

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.