AurFort
ComPacT NSX100...250Schneider Electric trip unit TM160D for ComPacT NSX 160/250 circuit breakers, thermal magnetic, rating 160 A, 4 poles 4d, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

TRIP UNIT

trip unit TM160D for ComPacT NSX 160/250 circuit breakers, thermal magnetic, rating 160 A, 4 poles 4d

SKU C254TM160

Schneider Electric C254TM160 is a trip unit in the ComPacT NSX100...250 range. Key specifications include poles: 4P; trip unit: TM-D; operational voltage: 690 V AC 50/60 Hz.

4PPoles
TM-DTrip unit
690 V AC 50/60 HzOperational voltage
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 18, 2026.

C254TM160 — selected manufacturer specifications
Product referenceC254TM160
RangeComPacT
Range of productComPacT NSX100...250
Product or component typeTrip unit
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Range compatibilityComPacT NSX250
Device applicationDistribution
Poles description4P
Protected poles description4D
Neutral positionLeft
Trip unit protection functionsLI
Protection typeL : for overload protection (thermal) I : for short-circuit protection (magnetic)
Trip unit rating160 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Circuit breaker mounting modeFixed
Long-time pick-up adjustment type Ir (thermal protection)Adjustable
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range120…400 s at 1.5 x In 15 s at 6 x Ir
Neutral protection settings1 x Ir (4D)
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range1250 A
Earth-leakage protectionWithout
StandardsEN/IEC 60947-2
Electrical shock protection classClass II
Pollution degree3 conforming to IEC 60947-1
IP degree of protectionIP40 conforming to IEC 60529
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.