TRIP UNIT

Trip unit MicroLogic 5.3 E for ComPacT NSX 400/630 circuit breakers, electronic, rating 400A, 3 poles 3d

SKU C4035E400

Schneider Electric C4035E400 is a trip unit in the ComPacT NSX400...630 range. Key specifications include poles: 3P; trip unit: MicroLogic 5.3 E; operational voltage: 690 V AC 50/60 Hz.

3PPoles
MicroLogic 5.3 ETrip unit
690 V AC 50/60 HzOperational voltage
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 18, 2026.

C4035E400 — selected manufacturer specifications
Product referenceC4035E400
RangeComPacT
Range of productComPacT NSX400...630
Product or component typeTrip unit
Trip unit nameMicroLogic 5.3 E
Trip unit technologyElectronic
Range compatibilityComPacT NSX400 ComPacT NSX630
Device applicationDistribution
Poles description3P
Protected poles description3D
Trip unit protection functionsLSI
Protection typeL : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection
Trip unit rating400 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Circuit breaker mounting modeFixed
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range160...400 A
Long-time protection delay adjustment type trAdjustable
[tr] long-time protection delay adjustment range15…400 s at 1.5 x Ir 0.35…11 s at 7.2 x Ir 0.5…16 s at 6 x Ir
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdAdjustable
[tsd] Short-time protection delay adjustment range0…0.4 s I²t=off 0.1…0.4 s I²t=on
Instantaneous protection pick-up adjustment type IiAdjustable
[Ii] instantaneous protection pick-up adjustment range1.5...12 x In
Earth-leakage protectionWithout
Zone selective interlocking ZSIWith
Local signallingFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Display typeLCD display
Type of measurementEnergy meter
Communication of dataEnergy metering Protection and alarm settings Time-stamped histories and event tables Instantaneous and demand values Maintenance indicators Demand current and power Power quality Maximeters/minimeters
Electrical data recordingMaintenance indicators
StandardsEN/IEC 60947-2
Electrical shock protection classClass II
Pollution degree3 conforming to IEC 60947-1
IP degree of protectionIP40 conforming to IEC 60529
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-40…85 °C

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.