AurFort
ComPacT NSX400...630Schneider Electric Trip unit MicroLogic 2.3 for ComPacT NSX 400/630 circuit breakers, electronic, rating 400A, 4 poles 4d, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

TRIP UNIT

Trip unit MicroLogic 2.3 for ComPacT NSX 400/630 circuit breakers, electronic, rating 400A, 4 poles 4d

SKU C4042D400

Schneider Electric C4042D400 is a trip unit in the ComPacT NSX400...630 range. Key specifications include poles: 4P; trip unit: MicroLogic 2.3; operational voltage: 690 V AC 50/60 Hz.

4PPoles
MicroLogic 2.3Trip unit
690 V AC 50/60 HzOperational voltage
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 18, 2026.

C4042D400 — selected manufacturer specifications
Product referenceC4042D400
RangeComPacT
Range of productComPacT NSX400...630
Product or component typeTrip unit
Trip unit nameMicroLogic 2.3
Trip unit technologyElectronic
Range compatibilityComPacT NSX400 ComPacT NSX630
Device applicationDistribution
Poles description4P
Protected poles description3D + N/2 4D 3D
Neutral positionLeft
Trip unit protection functionsLSoI
Protection typeL : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
Trip unit rating400 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Circuit breaker mounting modeFixed
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range160...400 A
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range11 s at 7.2 x Ir 16 s at 6 x Ir 400 s at 1.5 x Ir
Neutral protection settings0.5 x Ir (3D + N/2) 1 x Ir (4D) No protection (3D)
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdFixed
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range4800 A
Earth-leakage protectionWithout
Zone selective interlocking ZSIWithout
Local signallingFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
StandardsEN/IEC 60947-2
Electrical shock protection classClass II
Pollution degree3 conforming to IEC 60947-1
IP degree of protectionIP40 conforming to IEC 60529
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C