AurFort
ComPacT NSXSchneider Electric Circuit breaker, ComPacT NSX630N, 50kA/415VAC, 4 poles, MicroLogic 2.3 trip unit 630A, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

CIRCUIT BREAKER

Circuit breaker, ComPacT NSX630N, 50kA/415VAC, 4 poles, MicroLogic 2.3 trip unit 630A

SKU C63N42D630

Schneider Electric C63N42D630 is a circuit breaker in the ComPacT NSX range. Key specifications include rated current: 630 A at 40 °C; poles: 4P; trip unit: MicroLogic 2.3.

630 A at 40 °CRated current
4PPoles
MicroLogic 2.3Trip unit
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 06, 2026.

C63N42D630 — selected manufacturer specifications
Product referenceC63N42D630
RangeComPacT
Product nameComPacT NSX
Device short nameNSX630N
Product or component typeCircuit breaker
Device applicationDistribution
Poles description4P
Protected poles description4D 3D + N/2 3D
Neutral positionLeft
[In] rated current630 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 20 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Breaking capacity codeN 50 kA 415 V AC
Trip unit nameMicroLogic 2.3
Trip unit technologyElectronic
Trip unit protection functionsLSoI
Control typeToggle
Circuit breaker mounting modeFixed
[Ui] rated insulation voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service breaking capacity85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 42 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability15000 cycles
Electrical durability8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In
Power dissipation per pole39.7 W
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Upside connectionFront
Downside connectionFront
Connection pitch45 mm
Protection typeL : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
Trip unit rating630 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range250...630 A
Long-time protection delay adjustment type trFixed
[tr] long-time delay adjustment range400 s at 1.5 x Ir 16 s at 6 x Ir 11 s at 7.2 x Ir
Neutral protection setting0.5 x Ir (3D + N/2) 1 x Ir (4D) No protection (3D)
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdFixed
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range6900 A
Earth-leakage protectionWithout
Zone selective interlocking ZSIWithout
Number of slots6 slot(s)
Local signallingFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Width (W)185 mm
Height (H)255 mm
Depth (D)110 mm
Net weight8.13 kg
StandardsEN/IEC 60947-2
Overvoltage categoryIII
Electrical shock protection classClass II on front face
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Relative humidity0…95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating