AurFort
EasyPact CVSSchneider Electric circuit breaker, EasyPact CVS, 1000A, 36kA, 4P4D, 415V AC, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

CIRCUIT BREAKER

circuit breaker, EasyPact CVS, 1000A, 36kA, 4P4D, 415V AC

SKU E100F420FM

Schneider Electric E100F420FM is a circuit breaker in the EasyPact CVS range. Key specifications include rated current: 1000 A at 50 °C; poles: 4P; trip unit: ETS 2.0.

1000 A at 50 °CRated current
4PPoles
ETS 2.0Trip unit
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 18, 2026.

E100F420FM — selected manufacturer specifications
Product referenceE100F420FM
RangeEasyPact
Range of productEasyPact CVS
Product or component typeCircuit breaker
Device short nameCVS1000F
Device applicationLow voltage electrical distribution
Poles description4P
Protected poles description4D
Neutral positionLeft
Neutral protection settingNo protection (3D) 0.5 x Ir (3D + N/2) 1 x Ir (4D)
[Ue] rated operational voltage440 V AC 50/60 Hz
[In] rated current1000 A at 50 °C
Network typeAC
Network frequency50/60 Hz
[Ui] rated insulation voltage800 V AC conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-3
Power dissipation15 W
Protection typeL : for overload protection (long time) I : for instantaneous short-circuit protection
Breaking capacity codeF 36 kA 415 V AC
Local signalling4 LEDs (red) for fault indication 1 LED (yellow) for overload
Auxiliary contact composition1 NO/NC
Earth-leakage protectionWithout
Control typeRotary handle Toggle
Breaking capacity50 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
Utilisation categoryCategory A
[Ics] rated service breaking capacity50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability5000 cycles
Electrical durability3000 cycles at 415 V In 2000 cycles at 440 V In
Suitability for isolationYes conforming to EN/IEC 60947-2
Connection pitch70 mm
Mounting modeFixed
Mounting supportBackplate
Upside connectionFront
Downside connectionFront
Trip unit nameETS 2.0
Trip unit technologyElectronic
Trip unit protection functionsLI
Trip unit rating1000 A at 50 °C
Long time pick-up adjustment type IrAdjustable
Long time pick-up adjustment range0.4...1 x In
Long time delay adjustment typeAdjustable 9 settings
[tr] long-time delay adjustment range12.5…600 s at 1.5 x Ir 0.5…24 s at 6 x Ir 0.7…16.6 s at 7.2 x Ir
Thermal memory20 mn
Instantaneous pick-up adjustment type IiAdjustable
Instantaneous pick-up adjustment range1.5...10 x Ir
Zone selective interlocking ZSIWithout
Net weight18 kg
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Relative humidity0…95 %
Operating altitude0...2000 m without derating 2000...5000 m with derating
Height327 mm
Width280 mm
Depth147 mm
StandardsEN/IEC 60947-2
Product certificationsCCC CB CE
Pollution degree3 conforming to IEC 60664-1
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.