AurFort
EasyPact CVSSchneider Electric circuit breaker, EasyPact CVS, 1250A, 50kA, 3P3D, 415V AC, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

CIRCUIT BREAKER

circuit breaker, EasyPact CVS, 1250A, 50kA, 3P3D, 415V AC

SKU E125N320FM

Schneider Electric E125N320FM is a circuit breaker in the EasyPact CVS range. Key specifications include rated current: 1250 A at 50 °C; poles: 3P; trip unit: ETS 2.0.

1250 A at 50 °CRated current
3PPoles
ETS 2.0Trip unit
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 18, 2026.

E125N320FM — selected manufacturer specifications
Product referenceE125N320FM
RangeEasyPact
Range of productEasyPact CVS
Product or component typeCircuit breaker
Device short nameCVS1250N
Device applicationLow voltage electrical distribution
Poles description3P
Protected poles description3D
[Ue] rated operational voltage440 V AC 50/60 Hz
[In] rated current1250 A at 50 °C
Network typeAC
Network frequency50/60 Hz
[Ui] rated insulation voltage800 V AC conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-3
Power dissipation15 W
Protection typeL : for overload protection (long time) I : for instantaneous short-circuit protection
Breaking capacity codeN 50 kA 415 V AC
Local signalling4 LEDs (red) for fault indication 1 LED (yellow) for overload
Auxiliary contact composition1 NO/NC
Earth-leakage protectionWithout
Control typeRotary handle Toggle
Breaking capacity70 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 45 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
Utilisation categoryCategory A
[Ics] rated service breaking capacity70 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 45 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability5000 cycles
Electrical durability3000 cycles at 415 V In 2000 cycles at 440 V In
Suitability for isolationYes conforming to EN/IEC 60947-2
Connection pitch70 mm
Mounting modeFixed
Mounting supportBackplate
Upside connectionFront
Downside connectionFront
Trip unit nameETS 2.0
Trip unit technologyElectronic
Trip unit protection functionsLI
Trip unit rating1250 A at 50 °C
Long time pick-up adjustment type IrAdjustable
Long time pick-up adjustment range0.4...1 x In
Long time delay adjustment typeAdjustable 9 settings
[tr] long-time delay adjustment range12.5…600 s at 1.5 x Ir 0.5…24 s at 6 x Ir 0.7…16.6 s at 7.2 x Ir
Thermal memory20 mn
Instantaneous pick-up adjustment type IiAdjustable
Instantaneous pick-up adjustment range1.5...10 x Ir
Zone selective interlocking ZSIWithout
Net weight14 kg
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Relative humidity0…95 %
Operating altitude0...2000 m without derating 2000...5000 m with derating
Height327 mm
Width210 mm
Depth147 mm
StandardsEN/IEC 60947-2
Product certificationsCCC CB CE
Pollution degree3 conforming to IEC 60664-1
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C