AurFort
GoPact MCCB 200Schneider Electric Circuit breaker, GoPact MCCB 200, 3 poles, 36kA at 415VAC, 80A, TMD trip unit, adjustable thermal protection, up to 50°C, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

CIRCUIT BREAKER

Circuit breaker, GoPact MCCB 200, 3 poles, 36kA at 415VAC, 80A, TMD trip unit, adjustable thermal protection, up to 50°C

SKU G20F3A80

Schneider Electric G20F3A80 is a circuit breaker in the GoPact MCCB 200 range. Key specifications include rated current: 80 A at 40 °C; poles: 3P; trip unit: TM-D.

80 A at 40 °CRated current
3PPoles
TM-DTrip unit
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 06, 2026.

G20F3A80 — selected manufacturer specifications
Product referenceG20F3A80
Range of productGoPact MCCB
Product or component typeCircuit breaker
Product nameGoPact MCCB 200
Device applicationDistribution
Poles description3P
Protected poles description3D
[In] rated current80 A at 40 °C 80 A at 50 °C
[Ue] rated operational voltage415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
[Icu] rated ultimate short-circuit breaking capacity36 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
Performance levelF 36 kA 380/415 V AC
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Trip unit protection functionsLI
Control typeToggle
Circuit breaker mounting modeFixed
[Ui] rated insulation voltage440 V AC conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2
[Ics] rated service short-circuit breaking capacity36 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
Mechanical durability30000 cycles
Electrical durability8000 cycles at 415 V In
Power dissipation per pole16 W
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Upside connectionFront
Downside connectionFront
Connection terminalsscrew terminals
Connection pitch25 mm
Protection typeL : for overload protection (thermal) I : for short-circuit protection (magnetic)
Trip unit rating80 A at 40 °C 80 A at 50 °C
Long-time pick-up adjustment type Ir (thermal protection)Adjustable
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Long-time protection delay adjustment type trFixed
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range12 x In
Width (W)75 mm
Height (H)130 mm
Depth (D)60 mm
Net weight0.9 kg
ColourGrey (RAL 7035)
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H
Overvoltage categoryIII
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP20 conforming to IEC 60529
Ambient air temperature for operation-20…55 °C
Ambient air temperature for storage-35…85 °C
Operating altitude0...2000 m without derating 2000...5000 m with derating

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.