Schneider Electric G80N3E630 is a circuit breaker in the GoPact MCCB 800 range. Key specifications include rated current: 630 A at 40 °C; poles: 3P; trip unit: ETU.

630 A at 40 °CRated current
3PPoles
ETUTrip unit
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 17, 2026.

G80N3E630 — selected manufacturer specifications
Product referenceG80N3E630
Range of productGoPact MCCB
Product or component typeCircuit breaker
Product nameGoPact MCCB 800
Device applicationDistribution
Poles description3P
Protected poles description3D
[In] rated current630 A at 40 °C 630 A at 50 °C
[Ue] rated operational voltage415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
[Icu] rated ultimate short-circuit breaking capacity50 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 65 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
Performance levelN 50 kA 380/415 V AC
Trip unit nameETU
Trip unit technologyElectronic
Trip unit protection functionsLSI
Control typeToggle
Circuit breaker mounting modeFixed
[Ui] rated insulation voltage440 V AC conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to EN/IEC 60947-2
[Ics] rated service short-circuit breaking capacity50 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 65 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
Mechanical durability15000 cycles
Electrical durability3000 cycles at 415 V In
Power dissipation per pole50 W
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Upside connectionFront
Downside connectionFront
Connection terminalsscrew terminals
Connection pitch60 mm
Protection typeL : for overload protection (thermal) S : for short time short-circuit protection I : for instantaneous short-circuit protection
Trip unit rating630 A at 40 °C 630 A at 50 °C
Long-time pick-up adjustment type Ir (thermal protection)Adjustable
[Ir] long-time protection pick-up adjustment range0.25...1 x In
Long-time protection delay adjustment type trFixed
Short-time protection pick-up adjustment type IsdAdjustable
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdFixed
Instantaneous protection pick-up adjustment type IiAdjustable
[Ii] instantaneous protection pick-up adjustment range1.5...10 x In
Width (W)180 mm
Height (H)250 mm
Depth (D)105 mm
Net weight6.9 kg
ColourGrey (RAL 7035)
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H
Overvoltage categoryIII
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP20 conforming to IEC 60529
Ambient air temperature for operation-20…55 °C
Ambient air temperature for storage-35…85 °C
Operating altitude0...2000 m without derating 2000...5000 m with derating

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.