Schneider Electric catalog image for this SKU; may represent the product family.
CIRCUIT BREAKER
Thermal magnetic circuit breaker, TeSys GB2, 1P+N, 2 A, Icu 15 kA@240 V
SKU GB2CD07Schneider Electric GB2CD07 is a circuit breaker in the TeSys GB2 range. Key specifications include rated current: 2 A; poles: 1P + N; operational voltage: 250 V AC 50/60 Hz conforming to IEC 60947-2.
2 ARated current
1P + NPoles
250 V AC 50/60 Hz conforming to IEC 60947-2Operational voltage
PRODUCT DATA
Technical specifications
Source: Schneider Electric product catalog.
Verified September 18, 2026.
| Product reference | GB2CD07 |
|---|---|
| Range | TeSys |
| Product name | TeSys GB2 |
| Device short name | GB2 |
| Product or component type | Circuit breaker |
| Device application | Control |
| Poles description | 1P + N |
| Network type | AC/DC |
| Utilisation category | Category A conforming to IEC 60947-2 DC-12 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 |
| Network frequency | 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity | 10 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 25 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 |
| Trip unit technology | Thermal-magnetic |
| Magnetic tripping current | 26 A |
| Mounting mode | By clips |
| Mounting support | Plate Rail |
| Mounting position | Vertical Horizontal |
| Control type | Toggle |
| [In] rated current | 2 A |
| [Ue] rated operational voltage | 250 V AC 50/60 Hz conforming to IEC 60947-2 277 V AC 60 Hz conforming to CSA C22.2 No 235 277 V AC 60 Hz conforming to UL 1077 48 V DC |
| [Uimp] rated impulse withstand voltage | 4 kV conforming to IEC 60947-2 |
| Power dissipation per pole | 2 W |
| Mechanical durability | 8000 cycles |
| Electrical durability | 8000 cycles |
| Connections - terminals | Connector 1 cable(s) 0.75…6 mm²solid without cable end Connector 2 cable(s) 0.75…4 mm²solid without cable end Connector 1 cable(s) 0.75…4 mm²flexible with cable end Connector 2 cable(s) 0.75…2.5 mm²flexible with cable end |
| Tightening torque | 1.2 N.m on connector |
| Mechanical robustness | Shocks: 22 Gn for 20 ms conforming to IEC 60068-2-27 Vibrations: 5 Gn, 5...110 Hz conforming to IEC 60068-2-6 |
| Quantity per set | Set of 6 |
| 9 mm pitches | 2 |
| Height | 74 mm |
| Width | 15 mm |
| Depth | 67 mm |
| Net weight | 0.07 kg |
| Standards | EN/IEC 60947-1 EN/IEC 60947-2 CSA C22.2 No 235 UL 1077 |
| Product certifications | UL CSA |
| Protective treatment | TC |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Ambient air temperature for operation | -20…60 °C |
| Ambient air temperature for storage | -40…80 °C |
| Fire resistance | 960 °C conforming to IEC 60695-2-1 |
| Operating altitude | 3000 m |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.