CIRCUIT BREAKER
Motor circuit breaker,Easy TeSys Power,GZ1E,AC-3,3P,0.1..0.16A,thermal magnetic trip
SKU GZ1E01Schneider Electric GZ1E01 is a circuit breaker in the Easy TeSys Power range. Key specifications include poles: 3P; operational voltage: 690 V AC 50/60 Hz conforming to IEC 60947-2; current setting range: 0.1…0.16 A.
3PPoles
690 V AC 50/60 Hz conforming to IEC 60947-2Operational voltage
0.1…0.16 ACurrent setting range
PRODUCT DATA
Technical specifications
Source: Schneider Electric product catalog.
Verified September 17, 2026.
| Product reference | GZ1E01 |
|---|---|
| Range | Easy TeSys |
| Range of product | Easy TeSys Power |
| Product or component type | Circuit breaker |
| Device short name | GZ1E |
| Device application | Motor |
| Trip unit technology | Thermal-magnetic |
| Suitability for isolation | Yes conforming to IEC 60947-1 appendix 7.1.6 |
| Colour | Grey (RAL 7011) |
| Poles description | 3P |
| Network type | AC |
| Utilisation category | AC-3 |
| Network frequency | 50/60 Hz conforming to IEC 60947-2 |
| Mounting mode | By screws By clips |
| Mounting support | Rail |
| Mounting position | Any position |
| Breaking capacity | Icu: >= 100 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 Icu: >= 100 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 Icu: >= 100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 Icu: >= 100 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2 Icu: >= 100 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Control type | Push-button |
| Thermal protection adjustment range | 0.1…0.16 A |
| Magnetic tripping current | 1.5 A |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Power dissipation | 2.5 W (per pole) |
| Mechanical durability | 100000 cycles |
| Electrical durability | 100000 cycles for AC-3 |
| maximum operating rate | 25 cyc/h |
| Connections - terminals | Screw clamp terminals 2 1…6 mm² - cable stiffness: solid Screw clamp terminals 2 1.5…6 mm² - cable stiffness: flexible without cable end Screw clamp terminals 2 1…4 mm² - cable stiffness: flexible with cable end |
| Height | 89 mm |
| Width | 44.5 mm |
| Depth | 78 mm |
| Net weight | 0.26 kg |
| Standards | EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-4-1 GB/T 14048.1 GB/T 14048.2 GB/T 14048.4 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ |
| Product certifications | CB Scheme CCC CE EAC |
| Protective treatment | TH |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Ambient air temperature for operation | -20…60 °C |
| Ambient air temperature for storage | -40…80 °C |
| Fire resistance | 960 °C conforming to IEC 60695-2-1 |
| Operating altitude | 2000 m |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.