AurFort
Harmony KSchneider Electric cam star-delta switch - 3-pole - 60° - 32 A - screw mounting, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

COMPLETE CAM SWITCH

cam star-delta switch - 3-pole - 60° - 32 A - screw mounting

SKU K30H001YP

Schneider Electric K30H001YP is a complete cam switch in the Harmony K range. Key specifications include poles: 3P; ip protection: IP40 conforming to IEC 60529; net weight: 0.485 kg.

3PPoles
IP40 conforming to IEC 60529IP protection
0.485 kgNet weight
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 18, 2026.

K30H001YP — selected manufacturer specifications
Product referenceK30H001YP
Range of productHarmony K
Product or component typeComplete cam switch
Component nameK30
[Ith] conventional free air thermal current32 A
Mounting locationFront
fixing mode4 holes
Cam switch head typeWith front plate 64 x 64 mm
Type of operatorBlack handle
Rotary handle padlockingWithout
Presentation of legendWith metallic legend, 0 - Y - delta black marking
Cam switch functionStar-delta switch
ReturnWithout
Off positionWith Off position
Poles description3P
Switching positionsLeft: 0° - 300° Right: 0° - 60°
IP degree of protectionIP40 conforming to IEC 60529
Switching angle60 °
[Ui] rated insulation voltage690 V (pollution degree 3) conforming to IEC 60947-1
Short-circuit current5000 A
Short-circuit protection50 A cartridge fuse, type gG
[Uimp] rated impulse withstand voltage6 kV conforming to EN 947-1 6 kV conforming to IEC 947-1
Contact operationSlow-break
positive openingWith
Electrical connectionCaptive screw clamp terminals flexible, clamping capacity: 2 x 4 mm² Captive screw clamp terminals solid, clamping capacity: 2 x 6 mm²
Tightening torque1.2 N.m
Switching capacity in mA11000 mA DC at 120 V 2 contact(s) for inductive load (T = 50 ms) 11000 mA DC at 180 V 3 contact(s) for inductive load (T = 50 ms) 11000 mA DC at 60 V 1 contact(s) for inductive load (T = 50 ms) 1200 mA DC at 220 V 1 contact(s) for resistive load (T = 1 ms) 1200 mA DC at 440 V 2 contact(s) for resistive load (T = 1 ms) 1200 mA DC at 660 V 3 contact(s) for resistive load (T = 1 ms) 16000 mA DC at 140 V 3 contact(s) for inductive load (T = 50 ms) 16000 mA DC at 48 V 1 contact(s) for inductive load (T = 50 ms) 16000 mA DC at 95 V 2 contact(s) for inductive load (T = 50 ms) 23000 mA DC at 120 V 2 contact(s) for resistive load (T = 1 ms) 23000 mA DC at 180 V 3 contact(s) for resistive load (T = 1 ms) 23000 mA DC at 60 V 1 contact(s) for resistive load (T = 1 ms) 25000 mA DC at 30 V 1 contact(s) for inductive load (T = 50 ms) 25000 mA DC at 60 V 2 contact(s) for inductive load (T = 50 ms) 25000 mA DC at 90 V 3 contact(s) for inductive load (T = 50 ms) 3200 mA DC at 110 V 1 contact(s) for inductive load (T = 50 ms) 3200 mA DC at 220 V 2 contact(s) for inductive load (T = 50 ms) 3200 mA DC at 330 V 3 contact(s) for inductive load (T = 50 ms) 32000 mA DC at 140 V 3 contact(s) for resistive load (T = 1 ms) 32000 mA DC at 24 V 1 contact(s) for inductive load (T = 50 ms) 32000 mA DC at 24 V 1 contact(s) for resistive load (T = 1 ms) 32000 mA DC at 48 V 1 contact(s) for resistive load (T = 1 ms) 32000 mA DC at 48 V 2 contact(s) for inductive load (T = 50 ms) 32000 mA DC at 48 V 2 contact(s) for resistive load (T = 1 ms) 32000 mA DC at 70 V 3 contact(s) for inductive load (T = 50 ms) 32000 mA DC at 70 V 3 contact(s) for resistive load (T = 1 ms) 32000 mA DC at 95 V 2 contact(s) for resistive load (T = 1 ms) 400 mA DC at 440 V 1 contact(s) for resistive load (T = 1 ms) 400 mA DC at 660 V 2 contact(s) for resistive load (T = 1 ms) 6500 mA DC at 110 V 1 contact(s) for resistive load (T = 1 ms) 6500 mA DC at 220 V 2 contact(s) for resistive load (T = 1 ms) 6500 mA DC at 330 V 3 contact(s) for resistive load (T = 1 ms)
Mechanical durability300000 cycles
CAD overall width64 mm
CAD overall height64 mm
CAD overall depth119 mm
Net weight0.485 kg
StandardsIEC 60947-3
Product certificationsCULus 120 V 2 hp 1 phase CULus 240 V 5 hp 1 phase CULus 240 V 5 hp 3 phases CULus 480 V 20 hp 3 phases
Protective treatmentTC
Ambient air temperature for operation-25…55 °C
Ambient air temperature for storage-40…70 °C
Overvoltage categoryClass II conforming to IEC 60536 Class II conforming to NF C 20-030

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.