AurFort
ComPact NSX100...250Schneider Electric circuit breaker basic frame, ComPact NSX250F, 36 kA at 415 VAC 50/60 Hz, 250 A, without trip unit, 3 poles, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

BASIC FRAME

circuit breaker basic frame, ComPact NSX250F, 36 kA at 415 VAC 50/60 Hz, 250 A, without trip unit, 3 poles

SKU LV431403

Schneider Electric LV431403 is a basic frame in the ComPact NSX100...250 range. Key specifications include mounting mode: Fixed; rated current: 250 A at 40 °C; poles: 3P.

FixedMounting mode
250 A at 40 °CRated current
3PPoles
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 18, 2026.

LV431403 — selected manufacturer specifications
Product referenceLV431403
RangeComPact
Range of productComPact NSX100...250
Device short nameNSX250F
Product or component typeBasic frame
Device applicationDistribution
Circuit breaker nameCompact NSX250F
Number of poles3P
[In] rated current250 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
[Icu] rated ultimate short-circuit breaking capacity85 kA at 240 V AC 50/60 Hz conforming to UL 508 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 480 V AC 50/60 Hz conforming to UL 508 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 600 V AC 50/60 Hz conforming to UL 508
Performance levelF 36 kA 415 V AC
Control typeToggle
Mounting modeFixed
[Ui] rated insulation voltage800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability20000 cycles conforming to IEC 60947-2
Electrical durability10000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 10000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 20000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2 5000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2
Mounting supportBackplate
Upside connectionFront
Downside connectionFront
Connection pitch35 mm
Protection typeWithout protection
Width (W)105 mm
Height (H)161 mm
Depth (D)86 mm
StandardsEN/IEC 60947-2 UL 508
Product certificationsCSA UL
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.