AurFort
ComPact NSXSchneider Electric circuit breaker Compact NSX400N, 50 kA at 415 VAC, Micrologic 1.3 M trip unit 320 A, 3 poles 3d, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

CIRCUIT BREAKER

circuit breaker Compact NSX400N, 50 kA at 415 VAC, Micrologic 1.3 M trip unit 320 A, 3 poles 3d

SKU LV432749

Schneider Electric LV432749 is a circuit breaker in the ComPact NSX range. Key specifications include rated current: 320 A at 65 °C; poles: 3P; trip unit: MicroLogic 1.3 M.

Discontinued in the Schneider Electric IN catalog on 3 Jul 2023. Contact AurFort to confirm availability.

320 A at 65 °CRated current
3PPoles
MicroLogic 1.3 MTrip unit
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 06, 2026.

LV432749 — selected manufacturer specifications
Product referenceLV432749
RangeComPact
Product nameComPact NSX
Range of productComPact NSX400...630
Device short nameNSX400N
Product or component typeCircuit breaker
Device applicationMotor
Number of poles3P
Protected poles description3t
[In] rated current320 A at 65 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
[Icu] rated ultimate short-circuit breaking capacity85 kA at 240 V AC 50/60 Hz conforming to UL 508 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 600 V AC 50/60 Hz conforming to UL 508 50 kA at 480 V AC 50/60 Hz conforming to UL 508 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
Performance levelN 50 kA 415 V AC
Trip unit nameMicroLogic 1.3 M
Trip unit technologyElectronic
Trip unit protection functionsI
Control typeToggle
Circuit breaker mounting modeFixed
[Ui] rated insulation voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service short-circuit breaking capacity11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 42 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability15000 cycles
Electrical durability3000 cycles at 690 V In 6000 cycles at 690 V In/2 6000 cycles at 440 V In 12000 cycles at 440 V In/2
Mounting supportBackplate
Upside connectionFront
Downside connectionFront
Connection pitch45 mm
Protection typeI : for short-circuit protection (magnetic)
Trip unit rating320 A at 65 °C
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range3840 A 3200 A 2880 A 2560 A 1600 A 4160 A 3520 A 1920 A 2440 A
Short-time protection delay adjustment type tsdFixed
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range4800 A
Earth-leakage protectionWithout
Zone selective interlocking ZSIWithout
Number of slots for electrical auxiliaries6 slot(s)
Local signallingFlashing LED (green) for ready to operate
Width (W)140 mm
Height (H)255 mm
Depth (D)110 mm
Net weight6.05 kg
StandardsEN/IEC 60947
Product certificationsCCC EAC Marine
Overvoltage categoryClass II
Electrical shock protection classClass II
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Relative humidity0…95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.